EasyManua.ls Logo

Carrier 50TCQA06 - Unit Arrangement and Access; Return Air Filters

Carrier 50TCQA06
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3
UNIT ARRANGEMENT AND ACCESS
General
Fig. 1 and Fig. 2 show general unit arrangement and
access locations.
INDOOR BLOWER
ACCESS
CONTROL BOX
COMPRESSORS
(D08-12 only)
C09190
Fig. 1 Typical Access Panel Location (Front)
OUTDOOR-AIR OPENING
AND INDOOR COIL
ACCESS PANEL
COMPRESSOR
ACCESS PANEL
(04 - 07 only)
FILTER ACCESS
PANEL
C08449
Fig. 2 Typical Access Panel Locations (Rear)
Routine Maintenance
These items should be part of a routine maintenance
program, to be checked every month or two, until a
specific schedule for each can be identified for this
installation:
Quarterly Inspection (and 30 days after initial start):
Replace return air filter
Clean outdoor hood inlet filters
Check belt tension
Check belt condition
Inspect pulley alignment
Check fan shaft bearing locking collar tightness
Check outdoor coil cleanliness
Check condensate drain
Seasonal Maintenance
The following items should be checked at the beginning
of each season (or more often if local conditions and
usage patterns dictate):
Air Conditioning/Heat Pump:
Ensure outdoor fan motor mounting bolts are tight
Ensure compressor mounting bolts are tight
Inspect outdoor fan blade positioning
Ensure control box is clean
Check control box wiring condition
Ensure wire terminals are tight
Check refrigerant charge level
Ensure indoor coils are clean
Check supply blower motor amperage
Electric Heating:
Inspect power wire connections
Ensure fuses are operational
Ensure manualreset limit switch is closed
Economizer or Outside Air Damper
Check inlet filters condition
Check damper travel (economizer)
Check gear and dampers for debris and dirt
Air Filters and Screens
Each unit is equipped with return air filters. If the unit has
an economizer, it will also have an outside air screen. If a
manual outside air damper is added, it will also have a an
inlet air screen.
Each of these filters and screens will need to be
periodically cleaned or replaced.
RETURN AIR FILTERS:
EQUIPMENT DAMAGE HAZARD
Failure to follow this CAUTION can result in
premature wear and damage to equipment.
DO NOT OPERATE THE UNIT WITHOUT THE
RETURN AIR FILTERS IN PLACE.
Dirt and debris buildup on components can cause
premature wear on components resulting in
component failure.
CAUTION
Return Air Filters are disposable fiberglass filters. Access
to the filters is through the liftout filter access panel
located on the rear side of the unit, above the indoor coil
access panel. See Fig. 2.

Related product manuals