EasyManua.ls Logo

Carrier 50TCQA06 - Premierlink Control

Carrier 50TCQA06
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
38
Sensors Trouble LED is On:
1. Check the sensor’s Dirty LED. If it is flashing, the
sensor is dirty and must be cleaned.
2. Check the sensors cover. If it is loose or missing,
secure the cover to the sensor housing.
3. Replace sensor assembly.
Sensors Power LED is Off:
1. Check the controllers Power LED. If it is off,
determine why the controller does not have power
and make the necessary repairs.
2. Check the wiring between the sensor and the
controller. If wiring is loose or missing, repair or
replace as required.
Controllers Power LED is Off:
1. Ensure the circuit supplying power to the controller is
operational. If not, make sure JP2 and JP3 are set
correctly on the controller before applying power.
2. Verify that power is applied to the controllers supply
input terminals. If power is not present, replace or
repair wiring as required.
Remote Test/Reset Station’s Trouble LED Does Not
flash When Performing a Dirty Test, But the Control-
lers Trouble LED Does:
1. Verify that the remote test/station is wired as shown
in Fig. 53. Repair or replace loose or missing wiring.
2. Configure the sensor dirty test to activate the
controllers supervision relay. See “To Configure the
Dirty Sensor Test Operation” for details.
Sensors Trouble LED is On, But the Controllers
Trouble LED is OFF:
Remove JP1 on the controller.
Supply Air Temperature (SAT) Sensor — On
FIOPequipped 50TCQ unit, the unit is supplied with a
supplyair temperature (SAT) sensor (p/n:33ZCSENSAT).
This sensor is a tubular probe type, approx 6inches (12.7
mm) in length. It is a nominal 10k ohm thermistor. See
PremierLinkt Installation, StartUp and Configuration
Instructions. for temperatureresistance characteristic.
PREMIERLINK
E
CONTROL
The PremierLink controller (see Fig. 56) is compatible
with Carrier Comfort Network (CCN) devices. This
control is designed to allow users the access and ability to
change factorydefined settings, thus expanding the
function of the standard unit control board. CCN service
access tools include System Pilot, Touch Pilot and
Service Tool. Standard tier display tools Navigator and
Scrolling Marquee are not suitable for use with latest
PremierLink controller (Version 2.x).
The PremierLink control is factorymounted in the
50TCQ unit’s main control box to the left of the CTB.
Factory wiring is completed through harnesses connected
to the LVTB. Field connections are made at a 16pole
terminal block (TB1) located on the bottom shelf of the
unit control box in front of the PremierLink controller The
factoryinstalled PremierLink control includes the
supplyair temperature (SAT) sensor. The outdoor air
temperature (OAT) sensor is included in the
FIOP/accessory EconoMi$er 2 package.
Refer to Fig. 56 for PremierLink connection locations.
NOTE: Refer to PremierLinkt Installation, StartUp
and Configuration Instructions. Have a copy of this
manual available at unit startup.
C08199
Fig. 56 PremierLink Controller

Related product manuals