34
A
E
F
C
D
B
C08246
Fig. 52 Typical Smoke Detector System Wiring
Sensor and Controller Tests
Sensor Alarm Test
The sensor alarm test checks a sensors ability to signal an
alarm state. This test requires that you use a field provided
SDMAG test magnet.
OPERATIONAL TEST ALERT
Failure to follow this ALERT can result in an
unnecessary evacuation of the facility.
This test places the duct detector into the alarm state.
Unless part of the test, disconnect all auxiliary
equipment from the controller before performing the
test. If the duct detector is connected to a fire alarm
system, notify the proper authorities before
performing the test.
NOTICE
Sensor Alarm Test Procedure
1. Hold the test magnet where indicated on the side of
the sensor housing for seven seconds.
2. Verify that the sensors Alarm Light Emitting Diode
(LED) turns on.
3. Reset the sensor by holding the test magnet against
the sensor housing for two seconds.
4. Verify that the sensors Alarm LED turns off.
Controller Alarm Test
The controller alarm test checks the controllers ability to
initiate and indicate an alarm state.
OPERATIONAL TEST ALERT
Failure to follow this ALERT can result in an
unnecessary evacuation of the facility.
This test places the duct detector into the alarm state.
Unless part of the test, disconnect all auxiliary
equipment from the controller before performing the
test. If the duct detector is connected to a fire alarm
system, notify the proper authorities before
performing the test.
NOTICE
Controller Alarm Test Procedure
1. Press the controllers test/reset switch for seven
seconds.
2. Verify that the controllers Alarm LED turns on.
3. Reset the sensor by pressing the test/reset switch for
two seconds.
4. Verify that the controllers Alarm LED turns off.