EasyManua.ls Logo

Carrier 50TJ024 - Page 10

Carrier 50TJ024
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 2 Electrical Data (cont)
UNIT
50TJ
NOMINAL
VOLTAGE
(3 Ph,
60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM IFM
POWER
EXHAUST
ELECTRIC
HEAT*
POWER
SUPPLY
No. 1 No. 2
Min Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp FLA FLA LRA kW FLA MCA MOCP†
028
(25 Tons)
208/230 187 253 41.0 350 37.8 239 2 1 6.6 10.0 28.0/28.0
130/130 150/150
4.6 18.8 135/135 175/175
26/34 71/82 130/138 150/150
4.6 18.8 26/34 71/82 135/143 175/175
42/56 117/135 181/170 200/175
4.6 18.8 42/56 117/135 187/176 200/200
56/75** 156/180 191/215 200/225
4.6 18.8 56/75** 156/180 197/221 200/225
380 342 418 21.8 151 21.2 145 2 1 3.9 10.0 17.0
73 90
2.3 6.0 76 90
20 30 73 90
2.3 6.0 20 30 76 90
35 52 87 90
2.3 6.0 35 52 90 90
460 414 508 21.8 158 17.2 125 2 1 2.8 10.0 14.6
66 80
2.3 6.0 68 80
32 39 67 80
2.3 6.0 32 39 70 80
55 66 84 90
2.3 6.0 55 66 87 100
80** 96 114 125
2.3 6.0 80** 96 117 125
575 518 633 17.3 125 12.4 80 2 1 3.4 10.0 13.0
54 70
2.1 4.8 56 70
LEGEND
FLA Full Load Amps
HACR Heating, Air Conditioning and Refrigeration
IFM Indoor (Evaporator) Fan Motor
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
NEC National Electrical Code
OFM Outdoor (Condenser) Fan Motor
RLA Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v,
380 v, 480 v, and 575 v. Heaters are rated at 240 v, 380 v, 480 v, or
600 v. If power distribution voltage to unit varies from rated heater volt-
age, heater kW will vary accordingly.
†Fuse or HACR circuit breaker.
**Heaters are field installed only.
NOTES:
1. In compliance with NEC requirements for multimotor and combination
load equipment (refer to NEC Articles 430 and 440), the overcurrent
protective device for the unit shall be fuse or HACR breaker. The
Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%.
Use the following formula to determine the percent of
voltage imbalance.
% Voltage Imbalance =
max voltage deviation from average voltage
100 x
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
Determine maximum deviation from average voltage.
(AB) 457 452 = 5 v
(BC) 464 457 = 7 v
(AC) 457 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
7
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maxi-
mum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more
than 2%, contact your local electric utility company immediately.
3. MCA calculation for units with electric heaters over 50 kW
= (1.25 x IFM amps) + (1.00 x heater FLA).
10

Related product manuals