Performance data
COOLING CAPACITY
See page 15 for cooling notes.
HEATING CAPACITY
50ZH030 (2-1/2 TONS)
Temp (F)
Air Ent
Outdoor
coil (edb)
Indoor Entering Air—CFM/BF
875/0.10 1000/0.11 1125/0.12
Indoor Entering Air — Ewb (F)
72 67 63* 62 72 67 63* 62 72 67 63* 62
85
TC
31.6 29.2 27.1 26.4 32.2 29.6 27.5 26.9 31.9 29.9 27.8 27.2
SHC
15.0 19.8 19.5 23.9 15.7 20.9 20.7 25.4 15.9 22.0 21.7 26.6
kW
2.80 2.76 2.73 2.71 2.87 2.82 2.79 2.77 2.90 2.88 2.84 2.83
95
TC
30.9 28.1 26.0 25.3 31.2 28.2 26.4 25.7 31.4 28.8 26.7 26.1
SHC
15.0 19.4 19.1 23.4 15.6 20.6 20.3 24.9 16.1 21.7 21.3 26.0
kW
3.05 3.00 2.96 2.94 3.11 3.05 3.02 3.00 3.16 3.11 3.07 3.06
105
TC
29.7 26.9 24.8 24.1 30.0 27.2 25.1 24.5 30.1 27.5 25.4 25.1
SHC
14.6 19.0 18.6 22.8 15.2 20.2 19.8 24.2 15.7 21.4 20.9 25.1
kW
3.31 3.26 3.21 3.19 3.37 3.32 3.27 3.26 3.41 3.37 3.34 3.33
115
TC
28.4 25.5 23.5 22.9 28.7 25.8 23.8 23.4 28.8 26.1 24.0 24.0
SHC
14.2 18.6 18.1 22.2 14.9 19.8 19.2 23.4 15.4 20.9 20.3 24.0
kW
3.58 3.53 3.46 3.44 3.64 3.60 3.53 3.51 3.69 3.65 3.59 3.59
50ZH030
Temp (F)
Air Ent
Indoor
Coil
Indoor
Air CFM
(Std)
Air Temperature Entering Outdoor Coil (F db at 70% rh)
-100 1017203040475060
60
875
Cap.
9.13 8.40 11.5 10.6 14.1 13.0 16.1 14.7 17.0 15.4 20.4 17.8 24.2 24.2 27.5 27.5 28.6 28.6 33.9 33.9
kW
2.12 2.18 2.25
2.29 2.31
2.40 2.49 2.58
2.61 2.77
1000
Cap.
9.30 8.56 11.7 10.8 14.3 13.1 16.3 14.8 17.2 15.6 20.6 18.0 24.4 24.4 27.8 27.8 28.9 28.9 34.3 34.3
kW
2.15 2.20 2.26 2.30 2.32 2.39 2.48 2.56 2.59 2.73
1125
Cap.
9.46 8.70 11.9 10.9 14.5 13.3 16.4 15.0 17.4 15.8 20.8 18.2 24.6 24.6 28.0 28.0 29.2 29.2 34.6 34.6
kW
2.19 2.23 2.28 2.32 2.33 2.40 2.48 2.56 2.58 2.71
70
875
Cap.
8.62
7.93 11.1 10.2 13.8 12.7 15.8 14.4 16.7 15.1 20.0 17.5 23.7 23.7 26.9 26.9 28.0 28.0 33.1 33.1
kW
2.26 2.33 2.41
2.47 2.49
2.58 2.68 2.78
2.81 2.97
1000
Cap.
8.81
8.11 11.3 10.4 14.0 12.9 16.0 14.6 16.9 15.3 20.2 17.7 23.9 23.9 27.2 27.2 28.3 28.3 33.6 33.6
kW
2.29 2.35 2.42 2.47 2.49 2.57 2.66 2.75 2.78 2.92
1125
Cap.
8.97
8.25 11.5 10.5 14.2 13.0 16.2 14.7 17.1 15.5 20.4 17.9 24.2 24.2 27.5 27.5 28.6 28.6 33.9 33.9
kW
2.32 2.38 2.44 2.48 2.50 2.57 2.66 2.74 2.77 2.90
80
875
Cap.
7.99
7.35 10.6 9.71 13.3 12.2 15.5 14.1 16.4 14.9 19.6 17.2 23.2 23.2 26.3 26.3 27.4 27.4 32.4 32.4
kW
2.39 2.49 2.58
2.64 2.67
2.78 2.89 2.99
3.03 3.20
1000
Cap.
8.18
7.53 10.7 9.89 13.6 12.4 15.7 14.3 16.6 15.0 19.8 17.4 23.5 23.5 26.6 26.6 27.7 27.7 32.8 32.8
kW
2.42 2.51 2.59 2.65 2.67 2.77 2.87 2.96 2.99 3.14
1125
Cap.
8.36
7.69 10.9 10.1 13.8 12.6 15.9 14.5 16.8 15.2 20.0 17.6 23.7 23.7 26.9 26.9 28.0 28.0 33.2 33.2
kW
2.45 2.53 2.61 2.66 2.68 2.77 2.86 2.94 2.97 3.11
LEGEND
Cap. — Heating Capacity (1000 Btuh) (Includes Indoor-Fan Motor Heat)
db — Dry Bulb
kW — Total Power Input (Includes Compressor Motor Power Input
Outdoor-Fan Motor Input, and Indoor-Fan Motor Input)
rh — Relative Humidity
NOTES:
1. indicates integrated ratings
2. Integrated capacity is maximum (instantaneous) capacity less the
effect of frost on the outdoor coil and the heat required to defrost it.