Base unit dimensions 50ZH024,030
REQUIRED CLEARANCES TO COMBUSTIBLE MAT’L
Millimeters (in.)
Top of Unit ...................................0
Duct Side of Unit ...............................0
Side Opposite Ducts .............................0
Bottom of Unit .................................0
NEC REQUIRED CLEARANCES
Millimeters (in.)
Between Units, Power Entry Side .................1066.8 (42.00)
Unit and Ungrounded Surfaces, Power Entry Side ....... 914.0 (36.00)
Unit and Block or Concrete Walls and Other Grounded
Surfaces, Power Entry Side ....................1066.8 (42.00)
REQUIRED CLEARANCES FOR SERVICING
Millimeters (in.)
Outdoor Coil Access Side .......................762.0 (30.00)
Power Entry Side ............................762.0 (30.00)
(Except for NEC Requirements)
Unit Top ..................................914.0 (36.00)
Side Opposite Ducts ..........................762.0 (30.00)
LEGEND
NEC National Electrical Code
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-
fan discharge, with the exception of the outdoor coil (914 mm [36 in.]). A
removable fence or barricade requires no clearance.
2. Dimensions are in millimeters. Dimensions in ( ) are in inches.
3. is the center of gravity.
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WT CENTER OF GRAVITY mm (in.)
Lb Kg X Y Z
50ZH024 208/230-1-60 232 106 356 (14.0) 483 (19.0) 305 (12.0)
50ZH030 208/230-1-60; 208/230-3-60 254 116 356 (14.0) 483 (19.0) 305 (12.0)