J. Front Panel (supplied with chassis): Front
panel shall be constructed of a polymer material to
resist breakage and corrosion. It shall have a front
louvered surface with integrated control door and
air filters. The air filters shall be easily accessible
without removing the front panel from the chassis.
K. Air Filters: The chassis shall contain air filters,
with a minimum of 40% arrestance per ASHRAE
Standard 52.1. Two easily accessible front access
supply air filters, shall be interchangeable,
washable and permanent type. The vent filter shall
be a one--piece, removable and washable type
filter.
L. Bi--Directional Discharge Grille: Bi--directional
polymer discharge grille shall resist corrosion and
breakage. It shall be easily set to direct air at 40
degrees from horizontal or 80 degrees from
horizontal. This non--metallic discharge grille
shall be cool to the touch during the heating cycle.
M.Ventilation: The chassis shall have a manual
adjustable fresh air vent with a concealed manual
control. The vent control shall allow a maximum
of up to 65 CFM of fresh air to be drawn into the
room when the indoor fan is operating and the
door is open. The ventilation air can be increased
to approximately 95 CFM by adding the Booster
Ventilation accessory kit (see section S.13)
N. High Efficiency Condensate Removal System:
The chassis shall have a condensate removal
system consisting of a condensate suction port, to
draw and atomize condensate, and a slinger ring
integrated in the outdoor fan, to disperse
condensate onto t he condenser coil to be
evaporated.
O. 2 --piece Condenser Coil Shroud: The condenser
coil shroud shall be two pieces, to allow easy
access to service and maintain components in the
condenser section.
P. Accessories:
1. Power Cord (PN: PWRCORD--xxxV--xxA)
accessory, is required for all corded
applications.
2. Hardwire kit (PN: 52M--HDWR--KIT--xxA)
shall be required if an accessory power cord is
not used. The hardwire kit provides a permanent
connection to the unit and shall have 36 i nches
of flexible steel conduit and a plug --in connector
for easy connect/disconnect.
3. Insulated Polymer Wall Sleeve (PN:
SLEEVE--INSUL--1PK) shall be made from a
molded polymer, with factory installed
Styrofoam insulation and a minimum
flammability rating of UL94--5V. The sleeve
surface shall be textured to prevent shine and
hide scratches.
4. Deep Wall Metal Wall Sleeve (up to 28--in.)
(PN: SLEEVE--EXTxx--1PK) shall be a one--
piece, extended wall sleeve, with factory
installed insulation and deep wall baffles
integrated.
5. Sleeve Molding (PN: SLEEVE--MOLDING)
shall trim the wall sleeve to the existing wall to
hide wall joints and irregularities due to the
sleeve opening.
6. Architectural Grille
(PN:GRILLE -- PLA--xxxxx or
GRILLE -- ALU -- xxxxx)
shall be polymeric for long
durable life or painted aluminum for a superior
color match to the building.
7. Subbase (PN: SUBBASE--xxxV--xxA) shall be
pre--assembled from the factory and UL listed.
Subbase options include:
Non- electrical subbase: The
non--electrical subbase shall be
pre--assembled and provides
mechanical support and requires no
wiring.
Electrical subbase: The electrical
subbase shall be pre--assembled with
factory--i nstalled electrical junction
box containing a receptacle for corded
units.
8. Drain kit (PN: DRAIN--KIT--4PK): This
universal drain kit shall be used i nternally or
externally to route excess condensate to a
drainage system. It can be field--installed on any
Carrier wall sleeve. The drain kit shall be
attached to the exterior right or left side of the
wall sleeve for external draining or may be
mounted to the bottom of the wall sleeve for
internal draining. The drain kit shall include
both a straight tube and a 90 _ bend tube.
9. Wall Thermostats
(PN: PTACSTAT--NP--HC --A &
PTACSTAT-- NP--HP --A)
The digital wall
thermostat shall have a large LCD display with
backlighting, operate with 24VAC, be
non--programmable, easy to use and provide
maximum guest comfort.
10. Ventilation Booster
(PN: 52M-- PWRVENT-- DOOR):
The ventilation booster shall provide
approximately 95 CFM of outdoor air for
ventilation into the room. The kit shall have an
automatically door that opens when the booster
fan i s on and closes when the booster fan is off.
52M

Other manuals for Carrier 52M Performance Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier 52M Performance Series and is the answer not in the manual?

Carrier 52M Performance Series Specifications

General IconGeneral
BrandCarrier
Model52M Performance Series