EasyManua.ls Logo

Carrier 58MVP 170 Series - Status Code 24 Continued; Diagnosing Wiring Shorts for Status Code 24

Carrier 58MVP 170 Series
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
STEP ACTION YES NO GO TO
17 Replace the pressure switch assembly. 7
18 Is the high heat pressure switch HPS wired correctly? 20 19
19 Rewire high heat pressure switch HPS per wiring diagram. 7
20
Replace the pressure switch assembly and replace the vari-
able speed furnace control.
7
21
Check the inducer PWM line. To do this disconnect PL11
from the inducer motor and connect a DC voltmeter across
terminals PL11-2 BROWN (+) and PL11-10 YELLOW (-)
then run COMPONENT TEST by turning setup switch
SW1-6 ON. Does voltage across PL11-2 and PL11-10
change between states as shown below?
- State 1 - OFF (1.0 - 4.0 vdc)
- State 2 - MED (7.0 - 10.0 vdc)
22 15
22 Replace inducer motor or inducer motor assembly. 7
Status Code 24
SECONDARY VOLTAGE FUSE IS OPEN - Indicates fuse is open and there is a short in low-voltage wiring.
STEP ACTION YES NO GO TO
1 Turn power off and remove the blower access panel. 2
2
Is secondary voltage fuse blown? Check continuity to make
sure.
53
3 Replace variable speed furnace control. 4
4
Replace secondary voltage fuse if necessary then go to
page number indicated in Index for CLEANUP AND
START-UP INSTRUCTIONS.
INDEX
5
Disconnect all thermostat leads from the variable speed fur-
nace control (including all wires connected to the HUM ter-
minal) and replace secondary voltage fuse.
6
6
Replace the fuse, turn power on and depress door switch.
Use a piece of tape to hold switch closed.
7
7 Does status code 24 flash? 8 12
8
Turn power off and disconnect PL1 from variable speed fur-
nace control.
9
9
Do you have continuity between either RED wire connected
to the limit circuit and chassis ground?
10 3
10
You have a short circuit in the limit switch circuit. This in-
cludes limit switch LS, and flame roll-out switch FRS.
11
11 Fix problem. 4
12
Disconnect the pressure tube from the collector box and
jumper R and W/W1 thermostat terminals.
13
13
Does status code 24 begin flashing when W/W1 is ener-
gized?
14 21
14
Turn power off and disconnect PL1 from variable speed fur-
nace control.
15
15
Do you have continuity between the YELLOW wire con-
nected to the low heat pressure switch LPS and chassis
ground?
16 3
16
You have a short circuit in the low heat pressure switch cir-
cuit.
11
17
Does status code 24 begin flashing when the HUM terminal
is energized?
Note: On the variable speed furnace control the HUM termi-
nal is energized when the blower turns ON.
318
18
Disconnect jumper wire across R and W/W1 thermostat ter-
minals and wait until inducer stops.
19
19
Disconnect the pressure tube from the collector box and
jumper R, W/W1, and W2 thermostat terminals.
20
20
Does status code 24 begin flashing when W/W1 is ener-
gized?
34 37
21
Reconnect the pressure tube from the pressure switch as-
sembly back to the collector box.
22
22
Does status code 24 begin flashing when the low heat pres-
sure switch LPS is energized?
23 26
23
Turn power off and disconnect PL1 from variable speed fur-
nace control.
24
18

Table of Contents

Related product manuals