EXAMPLE 1:
Furnace ran for 16 minutes in low heat and 5 minutes in high heat during previous call for heat.
LH=16
HH=5
Calculate: (228 x 16) + (350 x 5) = 5398
3648 < 5398 < 5600 Calculate low heat run time for next cycle.
LH
run time
= (5600 - 5398) / 122 = 1.6 Next cycle, furnace will run for 2 minutes in low heat and then switch to high heat, if heat
call is still present.
EXAMPLE 2:
Furnace ran for 16 minutes in low heat and 10 minutes in high heat during previous call for heat.
LH=16
HH=10
Calculate: (228 x 16) + (350 x 10) = 7148
7148 5600 Next cycle furnace will only run in high heat, low heat run time is 0 min.
EXAMPLE 3:
Furnace ran for 13 minutes in low heat and 5 minutes in high heat during previous call for heat. This can happen if the furnace staging
algorithm calculated 13 minutes based on previous call for heat.
LH=13
HH=5
Calculate: (228 x 13) + (350 x 5) = 4714
3648 < 4714 < 5600 Calculate low heat run time for next cycle.
LH
run time
= (5600 - 4714) / 122 = 7.26 Next cycle, furnace will run for 7 minutes in low heat and then switch to high heat, if
heat call is still present.
EXAMPLE 4:
Furnace ran for 0 minutes in low heat and 10 minutes in high heat during previous call for heat.
LH=0
HH=10
Calculate: (228 x 0) + (350 x 10) = 3500
3500 < 3648 Next cycle furnace will only run in low heat for 16 minutes maximum, then switch to high heat, if heat call is still
present.