6
 
switched on automatically. When the room temperature 
reaches the degree selected on the thermostat, the furnace 
will be automatically switched off.
Some thermostats have a “fan” switch with 2 selections: 
AUTO or ON. When set on AUTO, the furnace blower 
cycles on and off, controlled by the thermostat. In the ON 
position, the furnace blower runs continuously except for 
a 45-sec delay at the “call for heat.” This keeps the tem-
perature level in your home more evenly balanced. It also 
continuously filters the indoor air.
 
Shutting down your furnace 
 
Should you ever suspect a malfunction in your furnace, 
you will need to turn the furnace off. The following pro-
cedures must be followed:
1. Set your room thermostat to the lowest temperature 
setting. (See Fig. 18.)
2. Close the external manual gas valve. (See Fig. 8 on 
page 5.)
3. Turn OFF the electrical power to your furnace. (See 
Fig. 19.) 
 
18                                      19
 
4. Remove the control access door on your furnace. (See 
Fig. 10 or 11.) On upflow furnaces, removing the 
blower access door is not required.
5. Turn the control knob on the gas valve to the OFF 
position. (See Fig. 20.)
6. Replace the control access door. (See Fig. 14 or 15.)
7. If the furnace is being shut down because of a mal-
function, call your dealer as soon as possible.
 
Performing routine maintenance
 
With the proper maintenance and care, your furnace will 
operate economically and dependably. Basic mainte-
nance, which can easily be accomplished by someone who 
follows the directions, is found on this and the following 
pages. However, before beginning maintenance, follow 
these safety precautions:
 
20
SYSTEM
COOL
OFF
HEAT
FAN
AUTO
ON
50
70
90
50
70
90
Filtering out trouble 
A dirty filter will cause excessive stress on the furnace 
blower motor and can cause it to overheat and automati-
cally shut down. The furnace filter should be checked 
every 3 or 4 weeks and cleaned if necessary.
If your furnace filter needs replacing, be sure to use the 
same size and type of filter that was originally supplied. 
Use the Furnace Filter Table and compare your furnace 
size with the proper filter size.
The air filter for upflow furnaces is normally located in the 
blower compartment. Filters for the downflow furnaces 
are normally located in the return air plenum above the 
blower. If the filters have been installed in another loca-
tion, contact your dealer for instructions. To inspect, clean 
and/or replace the air filter(s), follow these steps:
• Upflow Furnaces Only:
1. Turn OFF the electrical supply to the furnace. (See 
Fig. 19.)
2. Remove control and blower access doors.
21                                      22
3. Push filter retainer toward the bracket opening to 
release the filter. (See Fig. 21.) 
4. Gently remove the filter and carefully turn the dirty 
side up (if dirty) to avoid “spilling” dirt from the filter. 
(See Fig. 22.)
 
WARNING
 
Turn off electrical power supply to your furnace
before removing the access doors to service or
perform maintenance. A failure to follow this
warning could result in personal injury or death.
 
CAUTION
 
Although special care has been taken to minimize
sharp edges, be extremely careful when handling
parts or reaching into the furnace.
 
CAUTION
 
Never operate your furnace without a filter in
place. Doing so may damage the furnace blower
motor. An accumulation of dust and lint on inter-
nal parts of your furnace can cause a loss of effi-
ciency.
!
!
!