Step 3—Supply-Air Plenum Installation (Downflow)
INSTALLATION ON A CONCRETE SLAB
1. Construct hole in floor per dimensions in Fig. 4 and Table 3.
2. Install plenum and furnace as shown in Fig. 5.
INSTALLATION ON A COMBUSTIBLE FLOOR
1. Cut and frame hole in floor per dimensions in Installation
Instructions packaged with downflow subbase.
2. When completed, downflow subbase, plenum, and furnace (or
coil casing when used) should be installed as shown in Fig. 6.
Fig. 3—Air for Combustion and Ventilation
(Outside Air)
A93388
DUCTS TO
OUTDOORS
1 SQ IN.
PER 4000
BTUH
*
RETURN
AIR
VENT
THROUGH
ROOF
(CATEGORY I)
D
B
A
C
E
1 SQ IN.
PER 4000
BTUH
DUCT
TO
OUTDOORS
SUPPLY AIR
1 SQ IN.
PER 2000
BTUH
*
DUCTS
TO
OUTSIDE
12 MAX
12 MAX
CONFINED
SPACE
12″
MAX
12″
MAX
1 SQ IN.
PER 4000
BTUH
*
OUTDOORS
1 SQ IN.
PER 4000
BTUH
*
1 SQ IN.
PER 2000
BTUH
*
12 MAX
Use any of the following
combinations of openings:
A & B C & D D & E F & G
NOTE:
*
Minimum dimensions of 3-In.
F
G
For Example:
58RAV FURNACE
INPUT BTUH
FREE AREA PER
OPENING (SQ IN.)
ROUND PIPE
(IN. DIA)
46,000 11.5 4
69,000 17.3 5
92,000 23.0 6
115,000 28.8 7
135,000 34.5 7
For Example:
58RAV FURNACE
INPUT BTUH
FREE AREA PER
OPENING (SQ IN.)
ROUND PIPE
(IN. DIA)
46,000 23.0 6
69,000 34.3 7
92,000 46.0 8
115,000 57.6 9
135,000 69.0 10
Table 3—Opening Dimensions (In.)
FURNACE CASING
WIDTH
A
B
Heat-Only Heat/Cool*
14-3/16 13-1/8 19-5/8 19-7/16
17-1/2 16-7/16 19-5/8 19-7/16
21 19-7/8 19-5/8 19-7/16
24-1/2 23-7/16 19-5/8 19-7/16
* These dimensions apply when a model CB or CD Evaporator Coil casing is
to be installed.
Fig. 4—Floor Opening for Concrete Slab
A73382
HOLE IN
FLOOR
A
B
Fig. 5—Furnace on a Concrete Slab
(Non-Garage Installation)
A73383
FURNACE
PLENUM
5