Installation, Start-up, Operating and
Service and Maintenance Instructions
NOTE: Read the entire instruction manual before starting the
installation.
TABLE OF CONTENTS
REQUIRED NOTICE FOR MASSACHUSETTS INSTALLATIONS
IMPORTANT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Table 1 – Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Table 2 – Minimum Clearances to Combustible Materials
for All Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 3 – Loose Parts Bag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
CODES AND STANDARDS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS PROCE-
DURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
AIR FOR COMBUSTION AND VENTILATION . . . . . . . . . . . . . . 8
Table 4 – Minimum Free Area Required for Each Combustion Air
Opening or Duct to Outdoors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Table 5 – Minimum Space Volumes for 100% Combustion, Ventila-
tion and Dilution Air from Outdoors . . . . . . . . . . . . . . . . . . . . . . . 9
CONDENSATE TRAP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
CONDENSATE DRAIN CONNECTION . . . . . . . . . . . . . . . . . . . . 13
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Table 6 – Opening Dimensions - In. (mm) . . . . . . . . . . . . . . . . . 18
FILTER ARRANGEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Table 7 Filter Media Pressure Drop (Clean) Versus Airflow - in. w.c.
(Pa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 8 – Filter Media Pressure Drop (Clean) Versus Face Velocity-
in. w.c. (Pa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 9 – Air Filter Selection and Duct Sizing - In. (mm) . . . . . 21
AIR DUCTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
GAS PIPING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Table 10 – Maximum Capacity of Pipe . . . . . . . . . . . . . . . . . . . . 24
ELECTRICAL CONNECTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Table 11 – Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
ACCESSORIES (See Fig. 38) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
VENTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 12 – Vent Termination Kit for Direct Vent (2-pipe) Systems30
Table 13 – Approved Combustion-Air and Vent Pipe, Fitting and Ce-
ment Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Table 14 – Maximum Equivalent Vent Length - Ft. . . . . . . . . . . 40
Table 15 – Deductions from Maximum Equivalent Vent Length - Ft.
(M) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Table 16 – Maximum Allowable Exposed Vent Length in Uncondi-
tioned Space - Ft. / M. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Table 17 – Hanger Spacing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
AIR DELIVERY - CFM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Table 18 – Air Delivery - CFM (with filter) . . . . . . . . . . . . . . . . 48
Table 19 – Airflow Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
FURNACE CONTROL PROGRAMMING
AND NAVIGATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Table 20 – System Status Display Codes . . . . . . . . . . . . . . . . . . 52
Table 21 – Main Menu Options. . . . . . . . . . . . . . . . . . . . . . . . . . 53
SERVICE LABEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
START-UP, ADJUSTMENT, AND SAFETY CHECK . . . . . . . . . 55
Table 22 – Test Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Table 23 – Altitude Derate Multiplier for U.S.A. . . . . . . . . . . . . 58
Table 24 – Gas Rate (CU ft./hr). . . . . . . . . . . . . . . . . . . . . . . . . . 59
Table 25 Orifice Size and Manifold Pressure (in. w.c.) for Gas Input
Rate - 40,000 BTUh to 140,000 BTUh . . . . . . . . . . . . . . . . . . . . 60
Table 26 Orifice Size and Manifold Pressure (in. w.c.) for Gas Input
Rate - 26,000 BTUh ONLY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
SERVICE AND MAINTENANCE PROCEDURES. . . . . . . . . . . . 62
ELECTRICAL CONTROLS AND WIRING . . . . . . . . . . . . . . . . . 62
CARE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
WINTERIZATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
TROUBLSHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
PARTS REPLACEMENT INFORMATION GUIDE . . . . . . . . . . . 74
MODEL NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
TRAINING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
To learn more about this appliance and installation via a mobile device,
go to https://carrier.hvacpartners.com/NFC or use the QR code below. To
access airflow tables or troubleshooting guide on your mobile device go
to mlctraining.com/training/techdocs/28 or use the QR code below.
A220934
A200352
Portions of the text and tables are reprinted from NFPA 54/ANSI Z223.1E, with permission of National Fire Protection Association, Quincy, MA
02269 and American Gas Association, Washington DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSI
on the referenced subject, which is represented only by the standard in its entirety.
59SC6A
Single-Stage, High Efficiency, 4-Way Multipoise
35-in. (889 mm), Condensing Gas Furnace
Question and Answer IconNeed help?

Do you have a question about the Carrier 59SC6A and is the answer not in the manual?

Carrier 59SC6A Specifications

General IconGeneral
BrandCarrier
Model59SC6A
CategoryFurnace
LanguageEnglish

Summary

Required Notice for Massachusetts Installations

Introduction

Codes and Standards

Electrostatic Discharge (ESD) Precautions Procedure

Accessories

Location

Air for Combustion and Ventilation

Introduction

Overview of air requirements for combustion and ventilation.

Direct Vent (2-pipe) Applications

Details air needs for direct-vent systems.

Direct Vent (1-pipe) Applications

Details air needs for 1-pipe systems.

Ventilated Combustion Air Applications (for U.S. Only)

Specifies air requirements for ventilated applications.

Condensate Trap

Condensate Trap - Upflow Orientation

Explains trap setup for upflow installation.

Condensate Trap - Downflow Orientation

Details trap relocation for downflow installation.

Condensate Trap - Horizontal Orientation

Describes trap repositioning for horizontal installation.

Condensate Drain Connection

Upflow/Downflow Orientation

Covers drain routing for vertical furnace positions.

For Right Side Condensate Drain:

Provides step-by-step instructions for right-side drain.

Installation

Upflow Installation

Details furnace installation in upflow configuration.

Supply Air Connections

Explains how to connect supply air ducts.

Return Air Connections

Guides on connecting return air ducts.

Downflow Installation

Covers furnace installation in downflow configuration.

Filter Arrangement

Air Ducts

Gas Piping

Electrical Connections

Venting

Special Venting Requirements for Installations in Canada

Outlines specific Canadian venting regulations.

Configure the Furnace

Near Furnace Vent Connections

Addresses vent pipe routing near the furnace.

Install the Vent and Combustion Air Pipes

Guides on connecting vent and combustion air pipes.

Installing the Vent Pipe Adapter and Combustion Air Pipe Adapter

Installing the Vent Pipe Adapter and Combustion Air Pipe Adapter

Details installing vent and combustion air pipe adapters.

Furnace Control Programming and Navigation

On-Board Control Method

Explains control board interface and operation.

NFC and Supported App Method

Describes mobile app connectivity for control.

Control Board Replacement

Start-Up, Adjustment, and Safety Check

General

Provides general guidelines for start-up procedures.

Start-Up Procedures

Step-by-step instructions for starting the furnace.

Adjust Temperature Rise

Adjust Heating Blower-OFF Delay

Check Safety Controls

Service and Maintenance Procedures

Care and Maintenance

Blower Motor and Wheel Maintenance

Cleaning Burners and Flame Sensor

Servicing Hot Surface Igniter

Flushing Collector Box and Drainage System

Cleaning Condensate Drain and Trap

Checking Heat Pad Operation (If Applicable)

Cleaning Heat Exchangers

Winterization

Sequence of Operation

Troubleshooting

Gas Furnace Checklist

Parts Replacement Information Guide

Model Nomenclature

Training

Related product manuals