59SC6A: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
58
Table 23 – Altitude Derate Multiplier for U.S.A.
To  adjust  manifold  pressure  to  obtain  the  proper  input  rate,  first,
determine  if  the  furnace  has  the  correct  orifice  installed.  At  higher
altitudes or different gas heat contents, it may be necessary to change the
factory  orifice  to  a  different  orifice. Tables  have  been  provided  in  the
furnace  installation  instructions  to  match  the  required  orifice  to  the
manifold pressure to the heat content and specific gravity of the gas. To
do this:
1. Obtain  average  yearly  gas  heat  value  (at  installed  altitude)  from
local gas supplier.
2. Obtain average yearly gas specific gravity from local gas supplier.
3. Find installation altitude in Table 25 or Table 26.
4. Find closest natural gas heat value and specific gravity in Table 25
or Table 26. Follow heat value and specific gravity lines to point of
intersection to find orifice  size and  manifold pressure settings  for
proper operation.
5. Check and verify burner orifice size in furnace. NEVER ASSUME
ORIFICE SIZE. ALWAYS CHECK AND VERIFY.
6. Replace  orifice  with  correct  size,  if  required  by  Table 25  or
Table 26. Use only factory-supplied orifices. See EXAMPLE 1. 
EXAMPLE 1: 0 - 2000 ft. (0 - 609.6M) altitude
Heating value = 1050 Btu/cu ft.
Specific gravity = 0.62
Therefore: Orifice No. 44
Manifold pressure: 3.4-in. w.c. (847 Pa)
(Furnace  is  shipped  with  No.  44  orifices.  In  this  example,  all  main
burner  orifices  are  the  correct  size  and  do  not  need  to  be  changed  to
obtain proper input rate.)
NOTE:  To convert gas  manifold Table pressures to Pascals, multiply
the in. w.c. value by 249.1 Pa/in. w.c. (1 in. w.c. = 249.1 Pa).
Check Inlet Gas Pressure
The  inlet  gas  pressure  must  be  checked  with  the  furnace  operating  in
maximum  heat.  This  is  necessary  to  make  sure  the  inlet  gas  pressure
does not fall below the minimum pressure of 4.5 in. w.c.
1. Make  sure  the  gas  supply  is  turned  off  to  the  furnace  and  at  the
electric switch on the gas valve.
2. Loosen set screw on inlet tower pressure tap no more than one full
turn  with  a  3/32-in.  hex  wrench  or  remove  the  1/8-in.  NPT  plug
from the inlet pressure tap on the gas valve.
3. Connect a manometer to the inlet pressure tap on gas valve.
4. Turn on furnace power supply.
5. Turn gas supply manual shutoff valve to ON position.
6. Turn furnace gas valve switch to ON position.
7. Jumper  R  and  W  thermostat  connections  at  the  furnace  control
board.
8. When main burners ignite, confirm inlet gas pressure is between 4.5
in. w.c. (1125 Pa) and 13.6 in. w.c. (3388 Pa).
9. Remove jumper across thermostat connections to terminate call for
heat. Wait until the blower-OFF delay is completed.
10. Turn furnace gas valve electric switch to OFF position.
11. Turn gas supply manual shutoff valve to OFF position.
12. Turn off furnace power supply.
13. Remove manometer from the inlet pressure tap of the gas valve.
14. Tighten  set  screw  on  inlet  tower  pressure  tap  with  3/32-in.  hex
wrench,  or  if  1/8-in.  NPT  plug  was  removed,  apply  pipe  dope
sparingly to end of plug and re-install in the gas valve.
Adjust Manifold Pressure
NOTE:    There are  two  manifold  pressure  tables  in  these  instructions.
USE Table 26 FOR THE LOW CAPACITY 26,000 BTUh MODELS.
The low capacity model can be identified by the green label affixed to
the top of the gas valve. For all other models, see Table 25.
1. Adjust  manifold  pressure  to  obtain  proper  gas  input  rate.  See
Fig. 65.
a. Refer to the correct manifold pressure table for the appropriate 
model.
b. Turn gas valve ON/OFF switch to OFF.
c. Loosen set screw on manifold tower pressure tap no more than 
one full turn with a 3/32-in. hex wrench, or remove the 1/8 inch 
NPT plug from the manifold pressure tap on the gas valve.
d. Connect a water column manometer or similar device to 
manifold pressure tap.
e. Turn gas valve ON/OFF switch to ON.
f. Manually close blower door switch.
g. Jumper R and W thermostat connections on control to start 
furnace. See Fig. 38.
h. Remove regulator adjustment cap from gas valve pressure 
regulator and turn adjusting screw (3/16 or smaller flat-tipped 
screwdriver) counterclockwise (out) to decrease input rate or 
clockwise (in) to increase input rate. See Fig. 65.
i. When correct input is obtained, replace cap that conceals gas 
valve regulator adjustment screws. Main burner flame should be 
clear blue, almost transparent See Fig. 64.
j. Remove jumper R to W. 
A11461
Fig. 64 – Burner Flame
ALTITUDE  PERCENT 
OF
DERATE 
 DERATE
MULTIPLIER 
FACTOR
*
 
*. Derate multiplier factors are based on midpoint altitude for altitude range.
NOTE: For Canadian altitudes of 2000 to 4500 ft. (610 to 1372 M), use
USA  altitudes  of  2001  to  2000  ft.  (611  to  914  M)  in  Table 25  or
Table 26.
FT.  M
0–2000   0-610  0  1.00 
2001–3000   610-914  4-6  0.95
3001–4000   914-1219 6-8  0.93 
4001–5000   1219-1524 8-10 0.91 
5001–6000   1524-1829 10-12 0.89 
6001–7000   1829-2134 12-14 0.87 
7001–8000  2134-2438 14-16 0.85 
8001–9000  2438-2743 16-18 0.83 
9001–10,000  2743-3048 18-20 0.81 
WARNING
!
FIRE HAZARD
Failure  to  follow  this  warning  could  result  in  personal  injury,  death,
and/or property damage. 
Inlet  pressure  tap  set  screw  must  be  tightened  and  1/8-in.  NPT  pipe
plug must be installed to prevent gas leaks.
Burner Flame
Burner
Manifold