40
Table 10 — Coil Data (58T-110W) (cont)
39M UNIT SIZE 58T 61W 72W 85W 96W 110W
1-in. STEAM HEATING
Large Face Area
Nominal Capacity (cfm) at 700 fpm 40,163 42,467 49,933 58,800 66,150 75,600
Lower Coil Height (in.) 51 42 48 48 54 54
Upper Coil Height (in.) 51 42 48 48 54 54
Length (in.) 81 104 107 126 126 144
Total Face Area (sq ft) 57.4 60.7 71.3 84.0 94.5 108.0
Medium Face Area
Nominal Capacity (cfm) at 700 fpm 34,256 34,883 40,571 47,775 53,288 60,900
Lower Coil Height (in.) 45 36 39 39 45 45
Upper Coil Height (in.) 42 33 39 39 42 42
Length (in.) 81 104 107 126 126 144
Total Face Area (sq ft) 48.9 49.8 58.0 68.3 76.1 87.0
Small Face Area
Nominal Capacity (cfm) at 700 fpm 21,263 21,233
Height (in.) 54 42
Length (in.) 81 104
Total Face Area (sq ft) 30.4 30.3
Bypass Face Area (internal)
Nominal Capacity (cfm) at 700 fpm 25,988 27,300 32,769 38,588 44,100 50,400
Lower Coil Height (in.) 33 54 33 33 36 36
Upper Coil Height (in.) 33 N/A 30 30 36 36
Length (in.) 81 104 107 126 126 144
Total Face Area (sq ft) 37.1 39.0 46.8 55.1 63.0 72.0
5
/
8
-in. HOT WATER INTEGRAL FACE AND BYPASS
Nominal Capacity (cfm) 29,000 30,500 36,000 42,500 48,000 55,000
Coil Height (in.) 95 75 87 87 96 96
Length (in.) 70.4 92.4 92.4 114.4 114.4 136.4
Total Face Area (sq ft) 43.5 45.8 53.2 66.5 73.3 88.0
5
/
8
-in. STEAM INTEGRAL FACE AND BYPASS
Nominal Capacity (cfm) 29,000 30,500 36,000 42,500 48,000 55,000
Coil Height (in.) 95 75 87 87 96 96
Length (in.) 70.4 92.38 92.4 114.4 114.4 136.4
Total Face Area (sq ft) 43.5 45.8 53.2 66.5 73.3 88.0

Table of Contents