APPENDIX D — NETWORK CONFIGURATION (cont)
Table C — BACnet Object Table (cont)
OBJECT NAME OBJECT ID OPTION READ/WRITE DESCRIPTION
SETPOINT_EWT_OPT BV:39 RW EWT Control Option
SETPOINT_ice_sp AV:112 RW Ice Build Setpoint
SETPOINT_lcdw_sp AV:111 RW Heating LCDW Setpoint
SETPOINT_lcw_sp AV:109 RW Cooling LCW Setpoint
TEMP_cond_app AV:15 IR RO Condenser Approach
TEMP_COND_SAT AV:16 COV, IR RO Cond Sat Refrig Temp
TEMP_DGT AV:17 COV, IR RO Comp Discharge Temp
TEMP_DSH AV:18 RO Discharge Superheat
TEMP_ECDW AV:10 COV, IR RO Entering Condenser Water
TEMP_ECW AV:8 COV, IR RO Entering Chilled Water
TEMP_evap_app AV:14 IR RO Evaporator Approach
TEMP_EVAP_SAT AV:12 COV, IR RO Evap Sat Refrig Temp
TEMP_EVAP_T AV:13 COV, IR RO Evap Refrig Liquid Temp
TEMP_LCDW AV:11 COV, IR RO Leaving Condenser Water
TEMP_LCW AV:9 COV, IR RO Leaving Chilled Water
TEMP_MTRB AV:20 COV, IR RO Thrust Bearing Temp
TEMP_MTRB_OIL AV:19 IR RO Thrust Bearing Oil Temp
TEMP_MTRB1 AV:21 COV, IR RO Low Speed ME Brg Temp
TEMP_MTRB2 AV:22 COV, IR RO Low Speed CE Brg Temp
TEMP_MTRB3 AV:23 COV, IR RO High Speed ME Brg Temp
TEMP_MTRB4 AV:24 COV, IR RO High Speed CE Brg Temp
TEMP_MTRW1 AV:25 COV, IR RO Motor Winding 1 Temp
TEMP_MTRW2 AV:26 COV, IR RO Motor Winding 2 Temp
TEMP_MTRW3 AV:27 COV, IR RO Motor Winding 3 Temp
TEMP_OILT_DIS AV:29 COV, IR RO Oil Supply Temp
TEMP_OILT_SMP AV:28 COV, IR RO Oil Sump Temp
LEGEND
AV — Analog Value
BV — Binary Value
CMD— Commandable
COV — Change of Value
IR — Intrinsic Reporting
RO — Read Only
RW — Read/Write