100
APPENDIX D — NETWORK CONFIGURATION (cont)
Table C — BACnet Object Table (cont)
OBJECT NAME OBJECT ID OPTION READ/WRITE DESCRIPTION
MAISURGE_surg_act AV:82 RO Surge Prevention Active
MAISURGE_surg_pro AV:83 RO Surge Protection Active
OUTPUTS_ALE BV:19 RO Alert Relay
OUTPUTS_ALM BV:18 RO Alarm Relay
OUTPUTS_CHST_OUT AV:41 RO Chiller Stat Output mA
OUTPUTS_COMP_SR BV:20 RO Compressor Start Relay
OUTPUTS_exv_tgt AV:42 RO Oil EXV Target
OUTPUTS_GV1_DEC BV:21 RO Guide Vane 1 Decrease
OUTPUTS_GV1_INC BV:22 RO Guide Vane 1 Increase
OUTPUTS_hdpv_tgt AV:44 RO Head Pres Valve Tgt Pos
OUTPUTS_OIL_HEAT BV:23 RO Oil Heater Relay
OUTPUTS_OIL_PUMP BV:24 RO Oil Pump Relay
OUTPUTS_op_vfd_t AV:43 RO Oil Pump VFD Target
OUTPUTS_TFR_HIGH BV:25 RO Tower Fan Relay High
OUTPUTS_TFR_LOW BV:26 RO Tower Fan Relay Low
POWER_I_AMPS_A_I AV:51 RO Actual Line Current
POWER_I_AMPS_P_I AV:52 RO Percent Line Current
POWER_I_KW AV:55 RO Motor Kilowatts
POWER_I_POW_FACT AV:56 RO Motor Power Factor
POWER_I_VOLT_A AV:53 RO Actual Line Voltage
POWER_I_VOLT_P AV:54 RO Percent Line Voltage
POWER_O_alm_code AV:67 RO VFD Alarm Code
POWER_O_bus_volt AV:59 RO DC Bus Voltage
POWER_O_enc_temp AV:64 RO VFD Enclosure Temp
POWER_O_inv_temp AV:65 RO Inverter Temperature
POWER_O_lrtem_sw BV:30 RO LR Temp Switch
POWER_O_MOT_FREQ AV:58 RO Motor Actual Frequency
POWER_O_motor_kw AV:62 RO Motor Kilowatts
POWER_O_motor_pf AV:61 RO Motor Power Factor
POWER_O_motorkwh AV:63 RO Motor Kilowatt-Hours
POWER_O_prech_fd BV:29 RO Precharge Feedback
POWER_O_rec_temp AV:66 RO Rectifier Temperature
POWER_O_spd_fd BV:31 RO SPD Feedback
POWER_O_vfd_act AV:60 RO Actual VFD Speed Per
POWER_O_VFD_LOAD AV:57 RO VFD Load Current
POWER_O_VFDC_HI BV:32 RO High VFD Current
PRESSURE_COND_P AV:31 COV, IR RO Condenser Pressure
PRESSURE_DIFF_P AV:34 COV, IR RO Diffuser Pressure
PRESSURE_ECON_P AV:32 COV, IR RO Economizer Pressure
PRESSURE_EVAP_P AV:30 COV, IR RO Evaporator Pressure
PRESSURE_HEAD_P AV:35 COV, IR RO Head Pressure Reference
PRESSURE_OIL_PD AV:33 COV, IR RO Oil Pump Delta P
RUNTIME_C_STARTS AV:49 RO Compressor Starts Num
RUNTIME_SRV_HRS AV:50 RO After Service Hrs
SETPOINT_dem_base AV:113 RW Base Demand Limit
SETPOINT_ecdw_sp AV:110 RW Heating ECDW Setpoint
SETPOINT_ecw_sp AV:108 RW Cooling ECW Setpoint