APPENDIX D — NETWORK CONFIGURATION (cont)
Table C — BACnet Object Table (cont)
OBJECT NAME OBJECT ID OPTION READ/WRITE DESCRIPTION
GENUNIT_loc_occ BV:5 COV RO Local Schedule Occupied
GENUNIT_statstop BV:1 COV RO Deter Start Stop Command
HYDRLIC_CDW_FV AV:45 RO Cond Water Flow Value
HYDRLIC_cdw_pd AV:46 RO Condenser Water Delta P
HYDRLIC_CDWP BV:27 RO Condenser Water Pump
HYDRLIC_CHW_FV AV:47 RO Chilled Water Flow Value
HYDRLIC_chw_pd AV:48 RO Chilled Water Delta P
HYDRLIC_CHWP BV:28 RO Chilled Water Pump
INPUTS_DMP_ACT AV:36 RO
Damper Valve Status
Cl=0,Inter=1,Op=2,Fail=3
INPUTS_E_STOP BV:11 RO Emergency Stop Contact
INPUTS_FS_LOCK BV:16 RO Fire Security Interlock
INPUTS_GV1_ACT AV:38 RO Guide Vane 1 Actual Pos
INPUTS_HGBP_ACT AV:37
EC Valve Status
Cl=0,Inter=1,Op=2,Fail=3
INPUTS_HGBPACTP AV:40 RO Actual ECV Pos Per
INPUTS_HP_SW BV:9 RO High Pressure Switch
INPUTS_ICE_CON BV:12 RO Ice Build Contact
INPUTS_REM_CON BV:10 RO Remote Contact
INPUTS_REM_LOCK BV:13 RO Chiller Lockout
INPUTS_SAFETY BV:14 RO Spare Safety Input
INPUTS_STAR_AUX BV:8 RO Compressor Start Contact
INPUTS_STARTFLT BV:15 RO Starter Fault Feedback
INPUTS_TRIPR BV:17 RO ISM Trip Relay Status
INPUTS_VFD_ACT AV:39 RO Actual VFD Speed Per
LABONLY_gv1_fc BV:36 RO GV1 Forced
MAIN_MS_lag_s_s BV:35 RO Slave Start/Stop
MAIN_MS_lagstart AV:90 RO Lag Start Timer
MAIN_MS_lagstat AV:89 RO Slave Run Status
MAIN_MS_lagstop AV:91 RO Lag Stop Timer
MAIN_MS_lead_lag AV:87 RO
Unit is Lead or Lag
Disable=0, Lead=1, Lag=2
MAIN_MS_ll_comm BV:34 RO Lead Lag Communication
MAIN_MS_ll_fault AV:88 RO
Master Slave Fault
No Fault=0, Master=1
Slave=2, Both=3
MAIN_MS_ll_hr_d AV:94 RO Lead/Lag Hours Delta
MAIN_MS_preflt AV:92 RO Prestart Fault Timer
MAIN_MS_pulltime AV:93 RO Pulldown Timer
MAIN_SRD_diff_alm BV:33 RO SRD Rotating Stall Alarm
MAIN_SRD_lift_1 AV:85 RO VDO High Lift Load Line
MAIN_SRD_lift_2 AV:86 RO VDO Low Lift Load Line
MAIN_SRD_lift_a AV:84 RO Actual Lift
MAISURGE_act_reg AV:77 RO
Surge Region
No=0, Low=1, High=2
Deadband=3, Noise=4
MAISURGE_dts_act AV:78 RO Actual Delta Tsat
MAISURGE_dts_cal AV:79 RO Calc Ref Delta Tsat
MAISURGE_sc AV:80 RO Surge Counts
MAISURGE_spc AV:81 RO Surge Protection Counts