Table C — BACnet Object Table
OBJECT NAME OBJECT ID OPTION READ/WRITE DESCRIPTION
ALARMRST_alarm_1 AV:68 RO Jbus Current Alarm 1
ALARMRST_alarm_2 AV:69 RO Jbus Current Alarm 2
ALARMRST_alarm_3 AV:70 RO Jbus Current Alarm 3
ALARMRST_alarm_4 AV:71 RO Jbus Current Alarm 4
ALARMRST_alarm_5 AV:72 RO Jbus Current Alarm 5
CAPACTRL_cm_stat1 AV:76 COV, IR RO Comp1 Run State Val
CAPACTRL_ctrl_wt AV:73 RO Controlled Water Temp
CAPACTRL_gv1_tgt AV:74 RO Target GV1 Pos
CAPACTRL_vfd_tgt AV:75 RO Target VFD Speed Per
CFGSURGE_gv1_pful AV:96 RO IGV1 Full Load Position
CFGSURGE_gv1_pmin AV:95 RO IGV1 Minimum Position
CFGSURGE_sgl_hoff AV:99 RO Envelop Upper Deadband
CFGSURGE_sgl_loff AV:98 RO Envelop Lower Deadband
CFGSURGE_sgl_off AV:97 RO Envelop Line Offset
CFGSURGE_sgl_pro AV:103 RO Surge Profile Offset
CFGSURGE_sgl_shfh AV:100 RO Surge Line Shape Factor
CFGSURGE_sgl_shfl AV:101 RO Sound Line Shape Factor
CFGSURGE_sgl_spdf AV:102 RO Envelop Speed Factor
CONF_OPT_hgbp_opt AV:104 RO
EC Valve Option
No=0, Cont.=1,
ON/OFF=2, mA=3
CONF_OPT_hgbp_sel AV:105 RO
EC Selection
Disable=0, Surge=1
Low Load=2, Comb=3
CONNECT_bacena BV:37 RO BACnet Enable
CONNECT_bacunit BV:38 RO BACnet Metric Unit
CONNECT_ident AV:107 RO
BACnet Identifier
Call Home Configuration
CONNECT_network AV:106 RO BACnet Network
GENUNIT_AMPS_P AV:4 COV, IR RO Percent Load Current
GENUNIT_ch_state AV:7 RO Chiller Status Code
GENUNIT_CHIL_OCC_rd BV:3 COV, IR RO Network:Cmd Occupied
GENUNIT_CHIL_OCC_wr BV:42 CMD RW Network:Cmd Occupied
GENUNIT_CHIL_S_S_rd BV:2 COV RO Network:Cmd Start/Stop
GENUNIT_CHIL_S_S_wr BV:40 CMD RW Network:Cmd Start/Stop
GENUNIT_ctl_mode AV:1 COV, IR RO
Control Mode
Local=0, Network=1
Remote=2, Local Sched=3
GENUNIT_CTRL_PNT_rd AV:3 COV, IR RO Control Point
GENUNIT_CTRL_PNT_wr AV:114 CMD RW Control Point
GENUNIT_DEM_LIM_rd AV:6 COV RO Actual Demand Limit
GENUNIT_DEM_LIM_wr AV:115 CMD RW Actual Demand Limit
GENUNIT_EMSTOP_rd BV:4 COV RO Emergency Stop
GENUNIT_EMSTOP_wr BV:41 CMD RW Emergency Stop
GENUNIT_FC_START_rd BV:7 COV RO Start Free Cooling
GENUNIT_FC_START_wr BV:43 CMD RW Start Free Cooling
GENUNIT_HC_SEL_rd AV:2 COV RO Cooling/Heating Select
GENUNIT_HC_SEL_wr AV:116 CMD RW Cooling/Heating Select
GENUNIT_ice_occ BV:6 COV RO Ice Schedule Occupied
GENUNIT_KW_P AV:5 RO Motor Percent Kilowatts