APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Run Times
LEGEND
*Default value is shown only if configurable in this table.
NOTE: The displayed runtime is updated every hour. To avoid the
loss of data in case of disruption, the values are backed up.
Modes
LEGEND *Default value is shown only if configurable in this table.
Setpoint
LEGEND *Default value is shown only if configurable in this table.
CCN TABLE NAME: RUNTIME
PIC 5 PATH: Main Menu Run Times
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Starts in 12 Hours ST_CNT12 0 to 8 RO
2 Compressor Starts Num C_STARTS 0 to 99999 RO
3 Compressor Running Hrs COMP_HRS 0 to 500000.0 hr RO
4 After Service Hrs SRV_HRS 0 to 500000.0 0.0 hr RW
5 Stop to Start Timer spst_tim 1.0 to 15.0 min RO
6 Start to Start Timer stst_tim 4.0 to 45.0 min RO
7 Oil Lubrication Duration oilb_dur 1000 to 8000 hr RO
8 Oil Storage Duration oils_dur 5000 to 15000 hr RO
9 Recy Startup in 4 Hours RCYSTCNT 0 to 6 RO
10 Swift Restarts in 1 Hour SWIFTCNT 0 to 4 RO
RO Read Only
RW Read/Write
CCN TABLE NAME: MODES
PIC 5 PATH: Main Menu Modes
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Normal Shutdown shut_nor NO/YES RO
2 Recycle Shutdown shut_rcy NO/YES RO
3 Alarm Shutdown shut_alm NO/YES RO
4 Recycle Startup str_rcy NO/YES RO
5 Temperature Ramping tmp_ramp NO/YES RO
6 Load Ramping ld_ramp NO/YES RO
7 IGV1 Inhibiting gv1_inh NO/YES RO
8 Ice Building ice_act NO/YES RO
9 Ice Build Terminated ice_term NO/YES RO
10 Ice Build Recy Startup ice_rcy NO/YES RO
11 Ramp Loading ramp_act NO/YES RO
12 Demand Limit dem_act NO/YES RO
13 VFD Rampdown vfdrpact NO/YES RO
14 Demand Limit Inhibit dem_inh NO/YES RO
15 Evaporator Frozen evapfrze NO/YES RO
16 Condenser Frozen condfrze NO/YES RO
17 Recycle Shutdown Done rcysh_cm NO/YES RO
18 NonRecycle Shutdown Done nrysh_cm NO/YES RO
19 In Alarm alm_act NO/YES RO
20 In Override over_act NO/YES RO
21 Comp1 Run State Val cm_stat1 0 to 13 RO
RO Read Only
CCN TABLE NAME: SETPOINT
PIC 5 PATH: Main Menu Setpoint
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Cooling ECW Setpoint ecw_sp 15.0 to 120.0 60.0 °F RW
2 Cooling LCW Setpoint lcw_sp 10.0 to 120.0 45.0 °F RW
3 Heating ECDW Setpoint ecdw_sp 63.0 to 150.0 104.0 °F RW
4 Heating LCDW Setpoint lcdw_sp 68.0 to 150.0 113.0 °F RW
5 Ice Build Setpoint ice_sp 15.0 to 60.0 40.0 °F RW
6 Base Limit Demand dem_base 10.0 to 100.0 100.0 % RW
7 EWT Control Option EWT_OPT DSABLE/ENABLE DSABLE RW