APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Protective Limit Config
CCN TABLE NAME: CFGLIMIT
PIC 5 PATH: Main Menu Configuration Menu Protective Limit Config
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Evap Approach Alert evap_al 0.5 to 15 5 °F RW
2 Cond Approach Alert cond_al 0.5 to 15 6 °F RW
3 Cond Press Override Low cpov_lo 90 to 157 140 psig RW
4 Cond Press Override High cpov_hi 200 to 265 250 psig RW
5 Cond Press Cutout Low cpcut_lo 155 to 160 160 psig RW
6 Cond Press Cutout High cpcut_hi 270 to 275 275 psig RW
7 Evap Override Delta T ert_ovdt 2 to 5 3 °F RW
8 Evap Refrig Trippoint ert_trip 0 to 40 33 °F RW
9 High Evap Press Override ep_ov 90 to 157 140 psig RW
10 High Evap Press Cutout ep_cut 160 to 170 165 °F RW
11 Condenser Freeze Point cdfreeze –20.0 to 35.0 34.0 °F RW
12 Comp Discharge Alert dgt_alrt 125 to 200 200 °F RW
13 Comp Motor Temp Override mt_over 150 to 200 200 °F RW
14 Comp Bearing Temp Alert tb_alert 155 to 175 175 °F RW
15 Comp Bearing Temp Trip tb_trip 175 to 185 185 °F RW
16 Comp Bearing Alert XR6/7 tb_alt2 185 to 210 210 °F RW
17 Comp Bearing Trip XR6/7 tb_trip2 210 to 220 220 °F RW
18 Minimum Brine LWT bri_min 10 to 34 34 °F RW
19 Heating LWT Protect Set lwtp_sp 41 to 50 42.8 °F RW
20 Evap Flow Delta P Cutout evap_cut 0.5 to 50 5 psig RW
21 Cond Flow Delta P Cutout cond_cut 0.5 to 50 5 psig RW
22 Cond Hi Flow DP Limit cond_val 0.5 to 50 50 psig RW
23 Cond Hi Flow Alarm cond_alm DSABLE/ENABLE DSABLE RW