APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Option Configuration
LEGEND
*Default value is shown only if configurable in this table.
CCN TABLE NAME: CONF_OPT
PIC 5 PATH: Main Menu Configuration Menu Option Configuration
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Auto Restart Option astart DSABLE/ENABLE DSABLE RW
2 Common Sensor Option commsens DSABLE/ENABLE DSABLE RW
3 Water Pressure Option wp_opt DSABLE/ENABLE DSABLE RW
4EC Valve Option
0 = No, 1= Cont
2 = On/Off, 3 = 4-20 mA
hgbp_opt 0 to 3 0 RW
5 EC Selection
0 = Disable, 1 = Surge
2 = Low Load, 3 = Comb
hgbp_sel 0 to 3 0 RW
6 ECV Open IGV1 Position hpop_gv1 0.5 to 10 5.0 % RW
7 ECV Close IGV1 Position hgcl_gv1 1.5 to 20 10.0 % RW
8 ECV Off DT for Low Load hgb_toff 0.5 to 10.0 4.0 ^F RW
9 ECV On DT for Low Load hgb_ton 0.5 to 10.0 2.0 ^F RW
10 ECV Low Load DB hgbp_ldb 0.5 to 2.0 1.0 ^F RW
11 Head Pres Valve Option hdpv_opt DSABLE/ENABLE DSABLE RW
12 Head Pres Delta P 0% hdp_0 20.0 to 85.0 25.0 psig RW
13 Head Pres Delta P 100% hdp_100 20.0 to 85.0 50.0 psig RW
14 Head Pressure Min Output hdpv_min 0.0 to 100.0 0.0 % RW
15 Ice Build Option ice_opt DSABLE/ENABLE DSABLE RW
16 Ice Build Recycle ice_recy DSABLE/ENABLE DSABLE RW
17 Ice Build Termin Source
0 = Temp, 1 = Contact, 2 = Both
ice_term 0 to 2 0 RW
18 Tower Fan High set point tfh_sp 55 to 105 75 RW
19 Refrigerant Leak Option leak_en DSABLE/ENABLE DSABLE RW
20 Refrig Leakage Alarm mA exv_opt 4 to 20 20 RW
21 Oil EXV Option leak_ma DSABLE/ENABLE DSABLE mA RW
22 Oil Temp High Threshold oil_high 100 to 140 120 °F RW
23 Oil Temp Low Threshold oil_low 90 to 130 110 °F RW
24 Gas Torque Factor gt_fact 0.25 to 3.0 1 °F RW
25 Guide Vane/SRD Factor gv_srd_f 0.7 to 1.20 0.95 RW
26 Power Recovery Timeout pd_tcfg 0 to 60 15 min RW
27 Evap Liquid Temp Opt evap_ref DSABLE/ENABLE Enable
28 Evap App Calc Selection
Sat Temp = 0, Ref Temp = 1
evap_ref 0/1 1 RW
29 Condenser Flush Alert cfa_opt DSABLE/ENABLE DSABLE RW
30 Customer Alert Option cusa_opt DSABLE/ENABLE DSABLE RW
31 Water Flow Measurement
0 = No, 1 = Digital, 2 = Analog
wfm_opt 0-2 0 RW
32 Water Flow at 4 mA flow4ma 0-200 0.00 GPS RW
33 Water Flow at 20mA flow20ma 0-200 0.00 GPS RW
34 Evap Flow Rate Baseline chwf_bas 0-150 0.00 GPS RW
35 Evap Pres Drop Baseline evpd_bas 0-20 0.00 PSI RW
36 Cond Flow Rate Baseline cdwf_bas 0-150 0.00 PSI RW
37 Cond Pres Drop Baseline cdpd_bas 0-20 0.00 PSI RW
38 Water Pres Drop @ 20mA wpd_20ma 0-40 10.00 PSI RW
41 Vapor Source SV Delay vssv_dly 0-10 5.0 min RW
42 Max Oil Pressure Diff opvfdmax 35-60 50 PSI RW
43 Oil Pump VFD Max Step opvfdstp 0-10 7 % RW
44 Vapor Source SV Delay vssv_dly 0-10 5 min RW
45 Vapor Source SV Option vssv_dly DSABLE/ENABLE DSABLE RW
RW Read/Write