67
APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
ISM Configuration
LEGEND *Default value is shown only if configurable in this table.
CCN TABLE NAME: CONF_ISM
PIC 5 PATH: Main Menu Configuration Menu ISM Configuration
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Communication Timeout com_tout 0 to 255 10 sec RW
2 Starter Type
0 = Full Volt, 1 = Reduced Volt
2 = Solid State, 3 = FS VFD
star_typ 0 to 3 0 RW
3 Single Cycle Dropout scycd_en DSABLE/ENABLE DSABLE RW
4 Motor Rated Load Amps rla 10 to 5000 200 amp RW
5 Motor Rated Kilowatts rkw 1000 to 8000 1500 kW RW
6 Motor Locked Rotor Trip mot_lra 100 to 65535 1000 amp RW
7 Locked Rotor Start Delay lrs_del 1 to 10 5 cycles RW
8 Starter LRA Rating str_lra 100 to 65535 2000 amp RW
9 Motor Rated Line Voltage rlv 200 to 13800 460 V RW
10 Current Imbal Threshold cu_th 5 to 100 15 % RW
11 Voltage Imbal Threshold vu_th 1 to 10 5 % RW
12 Motor Current CT Ratio:1 ct_ratio 3 to 1000 100 RW
13 Volt Transformer Ratio:1 vt_rat 1 to 115 1 RW
14 Current Imbal Persist cu_per 1 to 10 5 sec RW
15 Voltage Imbal Persist vu_per 1 to 10 5 sec RW
16 Line Frequency Faulting lfref_en DSABLE/ENABLE DSABLE RW
17 Frequency (NO=50 Hz, YES=60 Hz) linefreq NO/YES NO RW
18 Ground Fault Protection gfp_en DSABLE/ENABLE ENABLE RW
19 Ground Fault Current gf_amps 1 to 25 15 amp RW
20 Ground Fault Persistence gfp_pers 1 to 10 5 cycles RW
21 Ground Fault Start Delay gfs_del 1 to 20 10 cycles RW
22 Ground Fault CT Ratio:1 gfct_rat 150 to 150 150 RW
23 Overvoltage Threshold ovvol_th 105 to 115 115 % RW
24 Undervoltage Threshold udvol_th 85 to 95 85 % RW
25 Over Under Volt Persist ovud_per 1 to 10 5 sec RW
26 Under Volt Start Delay uvs_del 1 to 4 1 sec RW
RW — Read/Write