APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Factory Parameters
General Configuration
LEGEND *Default value is shown only if configurable in this table.
VFD Parameters
CCN TABLE NAME: FACTORY
PIC 5 PATH: Main Menu Configuration Menu  Factory Parameters
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Factory Password fac_pass 0 to 65535 4444 RW
2 Chiller Type
0=19XR6/7, 1=19XR2-5/E/D/V
chil_typ 0 to 1 0 RW
3 Unit Type
0 = Cool Only, 1 = Heat Machine
unit_typ 0 to 1 0 RW
4 Refrigerant Type
0 = R134a, 1 = Low Pressure
refg_typ 0 to 1 0 RW
5Comp
0 = Single, 1 = Dual
comp_typ 0 to 1 1 RW
6 Cond Shell Side MAWP
0=185 psi, 1=300 psi
cond_typ 0 to 1 0 RW
7 Chilled Medium Type chmedium WATER/BRINE WATER RW
8 Country Code coun_cod 0 to 500 86 RW
9 Free Cooling Option freecool YES/NO NO RW
10 VFD Option
0 = No, 1 = FS FVD, 2 = UM VFD
vfd_opt 0 to 2 0 RW
11 IOB3 Option (19XR2-E/D/V) YES/NO YES RW
13 IOB4 Option hyd_opt YES/NO NO RW
14 Heat Reclaim Option heatrecl YES/NO NO RW
15 Guide Vane1 Type
0 = Digital, 1 = Analog
gv1_type 0 to 1 0 RW
16 VFD Feedback Voltage Sel
0 = 0 to 5 V, 1 = 0 to 10 V
vfd_fdv 0 to 1 0 RW
17 Electrical Damper Valve dmp_auto DSABLE/ENABLE DSABLE RW
18 Marine Option mrn_opt DSABLE/ENABLE DSABLE RW
19 Power Request Option pr_opt DSABLE/ENABLE DSABLE RW
20 Cont. Power Request cpr_opt DSABLE/ENABLE DSABLE RW
CCN TABLE NAME: GEN_CONF
PIC 5 PATH: Main Menu Configuration Menu  General Configuration
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 User Password 1 to 9999 1111 RW
2 Stop to Start Delay min_off 1 to 15 2 min RW
3 Start to Start Delay strt_dly 4 to 45 15 min RW
4 Demand Limit Type
0 = Base Demand, 1 = 4 to 20 mA
dem_sel 0 to 1 0 RW
5 Pulldown Ramp Type
0 = Temp, 1= Load
ramp_slct 0 to 1 1 RW
6 Demand Limit Source
0 = amps, 1 = kW
DEM_SLCT 0 to 1 0 RW
RW Read/Write
Freestanding VFD
CCN TABLE NAME: CFGGEVFD
PIC 5 PATH: Main Menu Configuration Menu  General VFD Config
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 VFD Gain vfd_gain 0.10 to 1.50 0.75 RW
2 VFD Max Speed Per vfd_max 90.0 to 110.0 100.0 % RW
3 VFD Min Speed Per vfd_min 65.0 to 100.0 70.0 % RW
4 VFD Start Speed Per vfd_str 65.0 to 100.0 100.0 % RW
5 VFD Current Limit vfdculm 0.0 to 99999.0 250 amp RW
6 VFD Load Current 20 mA vfdc20ma 10.0 to 5000.0 200.0 amp RW
7 Comp Frequency 100% comp_100 45.0 to 62.0 50.0 Hz RW
8 VFD Load Current Input vfd_ldap DSABLE/ENABLE ENABLE RW