APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Unit Mount VFD
SRD Configuration
LEGEND *Default value is shown only if configurable in this table.
CCN TABLE NAME: CFGUMVFD
PIC 5 PATH: Main Menu Configuration Menu  General VFD Config
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Compressor Speed 100% comp_hz 47 to 110 50 Hz RW
2 Rated Line Voltage rlv_i 200-13800 460 V RW
3 Motor Nameplate Current rla 10 to 1500 200 AMPS RW
4 Motor Nameplate Voltage rlv 200 to 13800 460 Volts RW
5 Motor Nameplate RPM rpm 1500 to 3600 3000 rpm RW
6 Motor Nameplate KW rlkw 0 to 5600 1500 KW RW
7 Skip Frequency 1 skipfrq1 0.0 to 102.0 102 Hz RW
8 Skip Frequency 2 skipfrq2 0.0 to 102.0 102 Hz RW
9 Skip Frequency 3 skipfrq3 0.0 to 102.0 102 Hz RW
10 Skip Frequency Band skipband 0.0 to 102.0 0 Hz RW
11 Motor Rated Load Current rla_load 10 to 1500 200 AMPS RW
12 Increase Ramp Time ramp_inc 5 to 60 30 sec RW
13 Decrease Ramp Time ramp_dec 5 to 60 30 sec RW
14 Line Voltage Imbalance% lvim_th 1 to 10 10 % RW
15 Line Volt Imbalance Time lvim_per 1 to 10 10 sec RW
16 Line Current Imbalance% lcim_th 5 to 40 40 % RW
17 Line Current Imbal Time lcim_per 1 to 10 10 sec RW
18 Motor Current Imbalance% mcim_th 5 to 40 40 % RW
19 Motor Current Imbal Time mcim_per 1 to 10 10 sec RW
20 Single Cycle Dropout scycd_en 0 to 1 0 RW
21 PWM Switch Frequency
0=2KHZ, 1=4KHZ
pwm_freq 0 to 1 0 RW
22 Restore Defaults res_def 0 to 1 0 RW
23 LEN Comm Timeout com_tout 0 to 255 10 sec RW
24 Modbus Comm Timeout mod_tout 0 to 255 2 sec RW
25 Gateway Modbus Baud Rate
4800=1, 9600=2, 19200=3, 38400=4
gw_baud 1 to 4 2 RW
CCN TABLE NAME: CONF_SRD
PIC 5 PATH: Main Menu Configuration Menu  SRD Configuration
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Diffuser Option diff_opt DSABLE/ENABLE DSABLE RW
2 SRD IGV Offset Select off_sel 1 to 5 3 RW
3 Low Lift Profile Select pro_sel 1 to 5 3 RW
4 Diffuser Full Span mA diff_ma 15.0 to 22.0 18.0 mA RW
5 GV1 Pos @ 25% Load gv11_25 0.0 to 83.0 6.4 % RW
6 GV1 Pos @ 50% Load gv11_50 0.0 to 83.0 22.9 % RW
7 GV1 Pos @ 75% Load gv11_75 0.0 to 83.0 41.3 % RW
8 SRD Pos @ 25% Load srd1_25 0.0 to 100.0 73.5 % RW
9 SRD Pos @ 50% Load srd1_50 0.0 to 100.0 35.1 % RW
10 SRD Pos @ 75% Load srd1_75 0.0 to 100.0 19.5 % RW
11 High Lift Load @ 100% lf1_100 0.0 to 100.0 67.5 °F RW
12 High Lift Load @ 25% lf1_25 0.0 to 100.0 52.4 °F RW
13 Low Lift Load @ 25% lf2_25 0.0 to 100.0 27.2 °F RW
14 Peak Detection Threshold peak_th 0.0000 to 5.0000 0.0000 Volts RW
RW Read/Write