74
APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Date/Time Configuration
Navigation: MAIN MENU CONFIGURATION MENU DATE/TIME CONFIGURATION
Network Configuration
LEGEND
*Default value is shown only if configurable in this table.
NOTES:
1. The BACnet network and the device object identifier can be mod-
ified. The default identifier has been chosen to easily recognize
the chiller on a BACnet network. The first two digits are the BAC-
net CARRIER vendor number (16). These parameters must be
unique on the BACnet network. They must be modified if more
than one Carrier chiller is connected to the BACnet network.
2. Changing one of these BACnet parameters will cause a reboot
of the board after 1 minute.
3. Changing IP address from the PIC 5 SETUP menu will require
a manual reboot or power cycle of the PIC 5 controller in order
to re-build the BACnet stack.
4. For more information, see Appendix D — Network Configura-
tion on page 95.
DATETIME - Date/Time Configuration
a19-2351
Fig. E — Date/Time Configuration Menu
CCN TABLE NAME: CONNECT
PIC 5 PATH: Main Menu Configuration Menu  CONNECT
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
Modbus Configuration
1 Modbus Option mb_opt DSABLE/ENABLE DSABLE RW
2 Modbus Server Type
0=IP, 1=RS485
ser_type 0/1 1 RW
3 Modbus Server UID ser_UID 1 to 255 1 RW
4 Modbus Metric Unit metric NO/YES YES RW
5 Modbus IP Port Number port_nbr 0 to 1024 502 RW
6 Modbus RS485 Config Parity Option
0=No Parity, 1=Odd Parity
2=Even Parity, 3= Force Parity Low
4 = Force Parity High
5= Multi Drop parity
parity 0 to 5 0 RW
7 Stop Bit Number
0= 1 Bit, 1= 2 Bits
stop_bit 0 to 1 0 RW
8 Modbus RS485 Baudrate baudrate 9600 to 38400 9600 RW
BACnet Configuration
9 BACnet Enable bacena DSABLE/ENABLE ENABLE RW
10 BACnet Metric Unit bacunit NO/YES YES RW
11 BACnet Network network 1 to 9999 1601 RW
12 BACnet Identifier Ident 0 to 9999999 1600001 RW
Call Home Configuration
13 Call Home Option ch_opt DSABLE/ENABLE DSABLE RW
14 Call Home IP Addr Part 1 ch_ip_P1 0 to 255 140 RW
15 Call Home IP Addr Part 2 ch_ip_P2 0 to 255 206 RW
16 Call Home IP Addr Part 3 ch_ip_P3 0 to 255 129 RW
17 Call Home IP Addr Part 4 ch_ip_P4 0 to 255 10 RW
RW Read/Write