APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Quick Test Menu
Navigation: MAIN MENU QUICK TEST
Quick Test
LEGEND *Default value is shown only if configurable in this table.
CCN TABLE NAME: QCK_TEST
PIC 5 PATH: Main Menu
Quick Test
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Quick Test Enable QCK_TEST DSABLE/ENABLE DSABLE RW
2 GV 1 Calibration Enable GV1_CAL DSABLE/ENABLE DSABLE RW
3 GV1 Calibration Status
0=No Calibration or Failure
1=In Progress, 2=Completed
GV1_STAT 0 to 2 RO
4 Guide Vane 1 Actual Ohms GV1_OHM 0.00 to 12000.00 RO
5 Guide Vane 1 Actual mA GV1_MAF 0.0 to 20.8 mA RO
6 Guide Vane 1 Tested Position Q_GV1POS 0.0 to 100.0 0.0 % RW
7 Quick Test GV1 Open Q_GV1OP OFF/ON OFF RW
8 Quick Test GV1 Close Q_GV1CL OFF/ON OFF RW
9 Quick Test Oil Pump Q_OILP OFF/ON OFF RW
10 Oil Pres Test Passed OP_PASS NO/YES RO
11 Oil Pump Delta Pressure OIL_PDQ –6.7 to 420.0 psig RO
12 Quick Test Oil Heater Q_OILH OFF/ON OFF RW
13 EC Valve Calib Enable HGBP_CAL DSABLE/ENABLE DSABLE RW
14 EC Valve Calib Status
0 = No Calib or Failure
1= Progress, 2 = completed)
HGBP_ST 0-2 RO
15 EC Valve Actual mA HGBP_AMA mA RO
16 Quick Test EC Valve Pos Q_HGBP_T 0-100 0.0 % RW
17 Quick Test ECV Open Q_HGBPOP OFF/ON OFF RW
18 Quick Test ECV Close Q_HGBPCL OFF/ON OFF RW
19 Quick Test Damper Open Q_DMPOP OFF/ON OFF RW
20 Quick Test Damper Close Q_DMPCL OFF/ON OFF RW
21 Quick Test Cond Pump Q_CDWP OFF/ON OFF RW
22 Condenser Water Flow CDW_FLOW NO/YES RO
23 Quick Test Chilled Pump Q_CHWP OFF/ON OFF RW
24 Chilled Water Flow CHW_FLOW NO/YES RO
25 Quick Test Head Val Pos Q_HDP 0.0 to 100.0 0.0 % RW
26 Quick Test Diffuser Pos Q_SRD 0.0 to 100.0 0.0 % RW
27 Quick Test Chiller Status Q_CHST 4.0 to 20.0 4.0 mA RW
28 Quick Test Oil EXV Q_EXV 4.0 to 20.0 4.0 mA RW
29 Condenser Water Delta T CDW_DT 40.0 to 245.0 °F RO
30 Chilled Water Delta T CHW_DT 40.0 to 245.0 °F RO
31 Guide Vane 1 Ohms 100% GV1_MAXO 0.00 to 12000.00 RO
32 Guide Vane 1 Ohms 0% GV1_MINO 0.00 to 12000.00 RO
33 Guide Vane 1 mA 100% GV1_MAXA 0.0 to 20.8 mA RO
34 Guide Vane 1 mA 0% GV1_MINA 0.0 to 20.8 mA RO
35 Quick Test VFD Cooling Q_VFDCOL OFF/ON OFF RW
36 EC Valve mA 100% HBP_MAXA 0.0 mA RO
37 EC Valve mA 0% HBP_MINA 0.0 mA RO
38 Quick Test Alarm Output Q_ALM OFF/ON OFF RW
39 Quick Test Alert Output Q_ALE OFF/ON OFF RW
40 Quick Test VFD Cooling Q_VFDCOL OFF_ON OFF RW
41 Quick Test Vapor SV Q_VAPSUC OFF/ON OFF RW
RO Read Only
RW Read/Write