APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Capacity Control
LEGEND *Default value is shown only if configurable in this table.
Override Control
LEGEND *Default value is shown only if configurable in this table.
CCN TABLE NAME: CAPACTRL
PIC 5 PATH: Main Menu Maintenance Menu Capacity Control
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Total Error + Resets tot_err °F RO
2 Control Point Error ctrl_err °F RO
3 Controlled Water Temp ctrl_wt °F RO
4 Control Point ctrl_pnt °F RO
5 Actual Set Point setpoint °F RO
6 Entering Water Change DT ewt_dt °F RO
7 Enter Water Temp Reset ewt_res °F RO
8 Leaving Water Temp Reset lwt_res °F RO
9 Discharge Gas Temp Reset dgt_res °F RO
10 Capacity Delta capa_dlt 0 to 100 % RO
11 Target GV1 Pos gv1_tgt % RO
12 GV1 Pos Change Delta gv1delta % RO
13 GV1 Change Flag
0 = Stop, 1 = Change, 2 = Cont
gv1_chg 0 to 2 RO
14 VFD Speed Change Flag
0 = Stop, 1 = Change, 2 = Cont
vfd_chg 0 to 2 RO
15 Target VFD Speed Percent vfd_tgt % RO
16 VFD Speed Change Delta vfd_dlta RO
17 EC Valve Target Percent hgbp_tp 0 to 100 % RO
18 Capacity Inhibit Flag cap_inh NO/YES RO
19 Capacity Decrease Flag cap_dec NO/YES RO
20 Condenser Water Delta T cdw_dt °F RO
21 Chilled Water Delta T chw_dt °F RO
22 Pulldown Set Point pull_set % RO
23 Demand Limit Inh Clamp deinhclm % RO
24 Ramping Demand Limit Val ramp_dem NO/YES RO
25 Compressor is Running comp_run NO/YES RO
26 Comp1 Run State Val cm_stat1 0 to 14 % RO
RO — Read Only
CCN TABLE NAME: OVERRIDE
PIC 5 PATH: Main Menu Maintenance Menu Override Control
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Capacity Inhibit cap_inho NO/YES RO
2 Capacity Decrease cap_deco NO/YES RO
3 High Condenser Pressure cpov_fl NO/YES RO
4 Low Discharge Superheat dshov_fl NO/YES RO
5 Low Suction Sat Temp sstov_fl NO/YES RO
6 High Motor Temp mtov_fl NO/YES RO
7 High Bearing Temp tbov_fl NO/YES RO
8 Low Source Temp lstov_fl NO/YES RO
9 High Discharge Temp dgtov_fl NO/YES RO
10 High Motor Current ampov_fl NO/YES RO
11 Required DSH dsh_req °F RO
12 Evap Sat Override Temp ert_over °F RO
13 IGV Step DSH Increase dshinstp % RO
14 IGV Step DSH Decrease dshdestp % RO
15 Cond Press Trip Value cp_trip psig RO
RO — Read Only