APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Surge Correction
Maintenance ISM Config
LEGEND *Default value is shown only if configurable in this table.
CCN TABLE NAME: MAISURGE
PIC 5 PATH: Main Menu Maintenance Menu Surge Correction
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Surge Region
0 = No, 1 = Low, 2 = High,
3 = Deadband, 4 = Noise
act_reg 0 to 2 RO
2 Active Delta Tsat dts_act ° F RO
3 Calc Ref Delta Tsat dts_cal °F RO
4 High Eff Delta Tsat dts_he °F RO
5 Amps Change Surge Prot amps_dta % RO
6 Max Amps Change Value amch_max % RO
7 Surge Counts sc RO
8 Surge Protection Counts spc RO
9 Surge Prevention Active surg_act NO/YES RO
10 Surge Protection Active surg_pro NO/YES RO
11 EC Vlave Change Flag
0 = Close, 1 = Hold, 2 = Open
hgbp_chg 0 to 2 RO
12 Cal Surge Delta Tsmax dts_maxc 0 to 150.0 °F RO
13 Cal Surge Delta Tsmin dts_minc 0 to 150.0 °F RO
14 Cal Surge Delta Tsmed dts_medc 0 to 150.0 ^F RO
15 IGV1 Full Load Position gv1_sful 0 to100.0 % RO
16 IGV1 Minimum Position gv1_smin 0.0 to 100.0 % RO
17 Opti-Sound IGV1 Position gvi_smed % RO
18 Envelop Line Optimized enlp_opt NO/YES RO
CCN TABLE NAME: ISM_MCFG
PIC 5 PATH: Main Menu Maintenance Menu Maintenance ISM Config
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 ISM Config Conflict ism_cflt NO/YES RO
2 Delete ISM Config del_ismc NO/YES NO RW
3 Communication Timeout com_tout 0 to 255 sec RO
High Eff Ref Delta Tsat dts_he ^F RO
4Starter Type
0=Full Volt, 1=Redu Volt
2=Solid State, 3=FS VFD
star_typ 0 to 3 RO
5 Single Cycle Dropout scycd_en DSABLE/ENABLE RO
6 Motor Rated Load Amps rla 10 to 5000 amp RO
7 Motor Locked Rotor Trip mot_lra 100 to 65535 amp RO
8 Locked Rotor Start Delay lrs_del 1 to 10 cycles RO
9 Starter LRA Rating str_lra 100 to 65535 amp RO
10 Motor Rated Line Voltage rlv 200 to 13800 V RO
11 Current Imbal Threshold cu_th 5 to 100 % RO
12 Voltage Imbal Threshold vu_th 1 to 10 % RO
13 Motor Current CT Ratio:1 ct_ratio 3 to 1000 RO
14 Volt Transformer Ratio:1 vt_rat 1 to 115 RO
15 Current Imbal Persist cu_per 1 to 10 sec RO
16 Voltage Imbal Persist vu_per 1 to 10 sec RO
17 Line Frequency Faulting lfref_en DSABLE/ENABLE RO
18 Frequency (No=50, Y=60Hz) linefreq NO/YES RO
19 Ground Fault Protection gfp_en DSABLE/ENABLE RO
20 Ground Fault Current gf_amps 1 to 25 amp RO
21 Ground Fault Persistence gfp_pers 1 to 10 cycles RO
22 Ground Fault Start Delay gfs_del 1 to 20 cycles RO
23 Ground Fault CT Ratio:1 gfct_rat 150 to 150 RO
24 Overvoltage Threshold ovvol_th 105 to 115 % RO
25 Undervoltage Threshold udvol_th 85 to 95 % RO
26 Over Under Volt Persist ovud_per 1 to 10 sec RO
27 Under Volt Start Delay uvs_del 1 to 4 sec RO
RO Read Only
RW Read/Write