80
Master Slave
Power Parameters
LEGEND *Default value is shown only if configurable in this table.
CCN TABLE NAME: MAIN_MS
PIC 5 PATH: Main Menu Maintenance Menu Master Slave
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Unit is Lead or Lag
0 = Disable
1 = Lead
2 = Lag
lead_lag 0 to 2 RO
2 Master Control Type
0 = Local
1 = Network
2 = Remote
3 = Local Sched
ms_ctrl 0 to 3 RO
3 Slave Control Type
0 = Local
1 = Network
2 = Remote
3 = Local Sched
sl_ctrl 0 to 3 RO
4 Lead Lag Communication ll_comm TRUE/FALSE RO
5 Master Slave Fault
0 = No Fault
1 = Master
2 = Slave
3 = Both
ll_fault 0 to 3 RO
6 Slave Run Status lagstat 0 to 14 RO
7 Slave Start/Stop lag_s_s START/STOP RO
8 Capacity Decrease CAP_DECL NO/YES RO
9 Capacity Inhibit CAP_INHL NO/YES RO
10 Master Chiller Running MST_RUN NO/YES RO
11 Local Surge Status LCL_SRG 0 to 3 RO
12 Remote Surge Status RMT_SRG 0 to 3 RO
13 EWT Control Option EWT_OPT DSABLE/ENABLE RO
14 Demand Limit Source
0 = Amps, 1 = KW
DEM_SLCT
0 to 1 RO
15 Lag Start Timer lagstart 0 to 60 min RO
16 Lag Stop Timer lagstop 0 to 60 min RO
17 Prestart Fault Timer preflt 0 to 30 min RO
18 Pulldown Timer pulltime 0 to 30 min RO
19 Pulldown: Delta T / Min pull_dt 0 to 100 °F RO
20 Lead/Lag Hours Delta ll_hr_d –99999 to 99999 hours RO
21 Overrid Control Point ctrpntov 10 to 160.0 °F RO
22 Overrid Act Demand Limit demlimov 10 to 100.0 % RO
CCN TABLE NAME: POWER_I
PIC 5 PATH: Main Menu Maintenance Menu Power Line Parameters
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Line Current Phase 1 LN_AMPS1 amp RO
2 Line Current Phase 2 LN_AMPS2 amp RO
3 Line Current Phase 3 LN_AMPS3 amp RO
4 Actual Line Current AMPS_A amp RO
5 Percent Line Current AMPS_P % RO
6 Ground Fault Phase 1 GRFT_1 amp RO
7 Ground Fault Phase 2 GRFT_2 amp RO
8 Ground Fault Phase 3 GRFT_3 amp RO
9 Line Voltage Phase 1 LN_VOLT1 V RO
10 Line Voltage Phase 2 LN_VOLT2 V RO
11 Line Voltage Phase 3 LN_VOLT3 V RO
12 Actual Line Voltage VOLT_A V RO
13 Percent Line Voltage VOLT_P % RO
14 Motor Kilowatts KW kW RO
15 Motor Kilowatts Hours KWH kW RO
16 Line Frequency LN_FREQ Hz RO
17 Power Factor POW_FACT RO
18 Line Current Imbalance% In_imb_i % RO
19 Line Voltage Imbalance% In_imb_v % RO
RO — Read Only