Alarm/Alert Codes
Table 10 lists PIC6 alert codes. Table 11 lists PIC6 alarm codes.
Alerts do not cause machine shutdown and are typically automati-
cally reset when the situation returns to normal, while alarms typi-
cally result in machine shutdown. See the Alarms menu in Fig. 60.
Fig. 60 — Alarm Menu
Displaying Alarms
The alarm icon on the interface (see the section Icons on
page 12) indicates unit status as follows:
• A flashing red icon shows that the unit is operating but
there is an alert.
• A steady red icon shows that the unit has been shut down
due to a fault.
The Current Alarms menu displays up to eight alarm codes that
are active on the unit. Table 11 lists alarm codes.
Resetting Alarms
When the cause of the alarm has been identified and corrected, the
alarm can be reset either automatically or manually (depending on
the type of alarm). To reset the alarms, enter the Reset Alarm
menu, select the Alarm Reset icon, select Yes in the pop-up win-
dow, and execute.
In the event of a power supply interrupt, if Auto Restart Option
is set to ENABLE in the Option Configuration menu, the unit re-
starts automatically without the need for an external command.
A manual reset must be run from the main menu via the Reset
Alarms Feature.
All information regarding solved alarms is stored in the Alarm
History. Alarm History stores last 50 alarms even after alarms
have been corrected or reset.
Table 10 — PIC6 Alert Codes
CODE
HITS TO
ACTIVATE
HITS TO
RESET
RESET TYPE RESPONSE MESSAGE TRIP CONDITION TROUBLESHOOTING
ALT003 10 10 AUTOMATIC Notify
ALT-003 Sensor Alert - Entering
Cond Water Temp
Entering condenser water
temperature (TEMP_ECDW) is
outside range.
Verify continuity to SIOB. Verify
voltage and ohm reading across
sensor. Replace sensor if ohm
reading is incorrect based on
temperature.
ALT004 10 10 AUTOMATIC Notify
ALT-004 Sensor Alert - Entering
Cond Water Press
Tested when the compressor is
on all of the run status:
If condenser flow detection type
(HYDRCFG_condfdtp) is set to
DeltaP (2)
AND
If entering condenser water
transducers voltage is outside
the range of 0.3V to 4.75V
Check 5V supply from IOB.
Check transducer output and
ground. Replace transducer if
voltage checks out good.
ALT005 10 10 AUTOMATIC Notify
ALT-005 Sensor Alert - Entering
Chilled Water Press
Tested when the compressor is
on all of the run status:
If evaporator flow detection type
(HYDRCFG_evapfdtp) is set to
DeltaP (2)
AND
If entering condenser water
transducers voltage is outside
the range of 0.3V to 4.75V
Check 5V supply from IOB.
Check transducer output and
ground. Replace transducer if
voltage checks out good.
ALT007 10 10 AUTOMATIC Notify
ALT-007 Sensor Alert - Leaving
Cond Water Temp
Leaving condenser water
temperature (TEMP_LCDW) is
outside range.
Verify continuity to SIOB. Verify
voltage and ohm reading across
sensor. Replace sensor if ohm
reading is incorrect based on
temperature.
ALT008 10 10 AUTOMATIC Notify
ALT-008 Sensor Alert - Leaving
Cond Water Press
Tested when the compressor is
on all of the run status:
If condenser flow detection type
(HYDRCFG_condfdtp) is set to
DeltaP (2)
AND
If entering condenser water
transducers voltage is outside
the range of 0.3V to 4.75V.
Check 5V supply from IOB.
Check transducer output and
ground. Replace transducer if
voltage checks out good.
ALT009 10 10 AUTOMATIC Notify
ALT-009 Sensor Alert - Leaving
Chilled Water Press
Tested when the compressor is
on all of the run status, If
evaporator flow detection type
(HYDRCFG_evapfdtp) is set to
DeltaP (2) AND If the entering
chilled water transducers
voltage is outside range.
Check 5V supply from IOB.
Check transducer output and
ground. Replace transducer if
voltage checks out good.