ALM506 0 4 MANUAL
Prevent Unit Startup or
Hard Stop
ALM-506 Protective
Limit - Low Condenser
Water Flow
Compressor operation is allowed
AND (HYDRCFG_cflo_vt) has
expired
AND IF (HYDRCFG_condfdtp) = 1
and (INPUTS_COND_FSW) is
FALSE
OR IF (HYDRCFG_condfdtp) = 2
and (PRESSURE_COND_WDP) <
(HYDRCFG_condfldp)
OR IF (HYDRCFG_condfdtp_ = 3
and (INPUTS_COND_FL)
<(HYDRCFG_condfgpm)
Verify setting in Hydronics
Configuration. Verify flow pressure
drop through unit.
ALM507 10 4 MANUAL
Prevent Unit Startup or
Hard Stop
ALM-507 Protective
Limit - Refrigerant Leak
REFRIGERANT LEAK OPTION is
ENABLED and REFRIGERANT
LEAK SENSOR > REFRIG LEAK
ALARM mA (leak_ma)
ALM508 10 4 MANUAL
Prevent Unit Startup or
Hard Stop
ALM-508 Protective
Limit - Spare Safety
Device
Spare safety input on SIOB goes to
Open when Spare Safety Option
Enabled Service Config menu
Spare Safety is Normally Closed i.e.,
Alarm if input is open
ALM509 0 0 MANUAL
Prevent Unit Startup or
Hard Stop
ALM-509 Protective
Limit - Stop Override
Stop override (stp_over) is enabled
ALM510 0 0 MANUAL
Prevent Unit Startup or
Hard Stop
ALM-510 Protective
Limit - Swift Restarts
Limit Exceeded
Chiller swift restart counter > 4 in one
hour
ALM511 0 0 MANUAL
Prevent Circuit Startup
or Hard Stop
ALM-511 Protective
Limit - Compressor
Motor Stall Cir A
A compressor stall is detected when
the MOTOR CURRENT
(DRVA1STS_MOT_CUR) OR
(STRTSTS_MOT_CUR) increases
by DELTA AMPS PERCENT over a
1 second interval.
If COMPRESSOR STALL COUNT
(CMPA1CTL_stall_ct) = 5 in STALL
TIME PERIOD chiller will shut down.
DELTA AMPS PERCENT = 10% and
STALL TIME PERIOD = 8 min.
ALM513 0 4 MANUAL
Prevent Circuit Startup
or Hard Stop
ALM-513 Protective
Limit - Condenser
Freeze Cir A
System maintains CRT
(TEMP_CND_ST_A) at or above the
Condenser Freeze Point subject to
ALL of the following:
Unit is not in pumpdown
(GENUNIT_STATUS != 11)
Unit is not in pumpdown lockout
(GENUNIT_STATUS != 12) with
Condenser Freeze Protection
disabled (HYDRCFG_cnd_fz_d)
CRT < Condenser Freeze Point
(3F). If evaporator fluid type is
set to water (SERVICE1_flui_typ
= 0), this alarm will be generated.
ALM515 0 4 MANUAL
Prevent Unit Startup or
Hard Stop
ALM-515 Protective
Limit - Evaporator
Freeze Cir A
System prevents unit from operating
if ANY of the following are TRUE:
EEFT (TEMP_ECW) < Fluid
Freeze Point + 0.55°C (F)
ELFT (TEMP_LCW) < Fluid
Freeze Point + 0.55°C (F)
ALM517 0 0 MANUAL
Prevent Unit Startup or
Hard Stop
ALM-517 Protective
Limit - High Discharge
Pressure Cir A
System maintains DST
(TEMP_DIS_ST_A) at or below the
maximum value given by the
Compressor Envelope
(CMPA1CTL_eDSTMx) at all times
during compressor operation.
ALM519 0 0 MANUAL
Prevent Unit Startup or
Hard Stop
ALM-519 Protective
Limit - High Suction
Pressure Cir A
System maintains SST
(TEMP_EVP_ST_A) at or below the
maximum value given by the
Compressor Envelope subject to
operation above compressor
envelope maximum SST
(CMPA1CTL_eSSTMx) 1 hour
cumulative
ALM521 10 4 MANUAL
Prevent Circuit Startup
or Hard Stop
ALM-521 Protective
Limit - High Condenser
Pressure Cir A
System maintains Condenser
Pressure (PRESSURE_CND_P_A)
at or below Condenser Maximum
Pressure* subject to ALL of the
following:
Unit is not in pumpdown
(GENUNIT_STATUS != 11)
Unit is not in pumpdown lockout
(GENUNIT_STATUS != 12) with
Condenser Freeze Protection
(HYDRCFG_cnd_fz_d) disabled
*Default 1000 kPa (145 psi) - FIXED
Table 11 PIC6 Alarm Codes (cont)
CODE
HITS TO
ACTIVATE
HITS TO
RESET
RESET TYPE RESPONSE MESSAGE TRIP CONDITION TROUBLESHOOTING