44
APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (cont)
LEGEND
LEGEND
Drive A Status
CCN TABLE NAME: DRVA1STS
PIC6 PATH: Main Menu Status Menu Drive A Status
LINE PIC6 DESCRIPTION CCN NAME RANGE DEFAULT VALUE
a
NOTE(S):
a. Default value is shown only if configurable.
UNIT READ/WRITE
1
VFD Coms Status
0=OK, 1=PARTIAL, 2=NO COMS
COMS 0 to 2 — RO
2 VFD Coms Status Text coms_txt CHARS8 — RO
3 VFD Average Line Voltage LINE_V V RO
4 VFD Average Line Current LINE_CUR A RO
5 VFD Average Line KW LINE_KW kW RO
6 VFD Bus Voltage BUS_V V RO
7 VFD Motor Current MOT_CUR A RO
8 VFD Motor Curr Pct Rated AMPS_PCT % RO
9 VFD Motor KW MOT_KW kW RO
10 VFD Capacity PCT % RO
11 VFD Speed SPD Hz RO
12 VFD Inverter Temp INV_T °F RO
13 VFD IGBT Temp IGBT_T °F RO
14 VFD Rectifier Temp RECT_T °F RO
15 VFD Motor Rpm MOT_RPM rpm RO
16 VFD Last Fault Code LAST_FLT — RO
17 VFD Status Word1 STAT_WD1 — RO
18 VFD Status Word2 STAT_WD2 — RO
19 VFD Alert Word1 ALT_WD1 — RO
20 VFD Alert Word2 ALT_WD2 — RO
21 VFD Alarm Word1 ALM_WD1 — RO
22 VFD Alarm Word2 ALM_WD2 — RO
RO — Read Only
Hydronics Status
CCN TABLE NAME: HYDRSTS
PIC6 PATH: Main Menu Status Menu Hydronics Status
LINE PIC6 DESCRIPTION CCN NAME RANGE DEFAULT VALUE
a
NOTE(S):
a. Default value is shown only if configurable.
UNIT READ/WRITE
Evaporator
1 Chill Water Pump CHWP1 NO_YES — RO
2 Flow Established ehas_flo 0 to 1 — RO
3 Evaporator Flow Switch EVAP_FSW OFF_ON — RO
4 Entering Evap Water Pres EVAP_EWP OFF_ON PSIG RO
5 Leaving Evap Water Pres EVAP_LWP NO_YES PSIG RO
6 Evap Water Delta P EVAP_WDP NO_YES PSIG RO
7 Actual Evap GPM aegpm GPM RO
Condenser
1 Cond Water Pump CDWP1 NO_YES — RO
2 Flow Established chas_flo NO_YES — RO
3 Condenser Flow Switch COND_FSW 0 to 1 — RO
4 Entering Cond Water Pres COND_EWP 0 to 0 PSIG RO
5 Leaving Cond Water Pres COND_LWP PSIG RO
6 Cond Water Delta P COND_WDP PSIG RO
7 Actual Cond GPM acgpm GPM RO
RO — Read Only