49
APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (cont)
LEGEND
Drive A Configuration
CCN TABLE NAME: DRVA1CFG
PIC6 PATH: Main Menu Configuration Menu
Circuit A Config Menu Drive A Config
LINE PIC6 DESCRIPTION CCN NAME RANGE DEFAULT VALUE
a
NOTE(S):
a. Default value is shown only if configurable.
UNIT READ/WRITE
1 Rated Line Voltage rlv_i
0 to 0 460 V
RW
2 Motor Rated Load Amps rla_m
10 to 5000 200 A
RW
3 Motor Nameplate Voltage rlv
0 to 0 460 V
RW
4 Motor Nameplate Current rla
0 to 0 200 A
RW
5 Motor Nameplate RPM rlrpm
0 to 0 3000 rpm
RW
6 Motor Nameplate KW rlkw
0 to 0 1500 kW
RW
7 Compressor 100% Speed rlhz
0 to 200 90 Hz
RW
8 Compressor Unload Spd min_spd
0 to 0 20 Hz
RW
9 Compressor Start Spd strt_spd
0 to 0 25 Hz
RW
10 Torque Limit Percent torq_lim
0 to 0 115 %
RW
11 Current Limit Percent curr_lim
0 to 0 110 %
RW
12 PWM Switch Frequency pwm_freq
0 to 0 2 kHz
RW
13 Skip Frequency 1 skipfrq1
0 to 0 30 Hz
RW
14 Skip Frequency 2 skipfrq2
0 to 0 30 Hz
RW
15 Skip Frequency 3 skipfrq3
0 to 0 30 Hz
RW
16 Skip Frequency Band skipband
0 to 0 0 Hz
RW
17 Increase Ramp Time ramp_inc
0 to 0 100 sec
RW
18 Decrease Ramp Time ramp_dec
0 to 0 10 sec
RW
Lube A Config
CCN TABLE NAME: LUBECFGA
PIC6 PATH: Main Menu Configuration Menu
Circuit A Config Menu Lube A Config
LINE PIC6 DESCRIPTION CCN NAME RANGE DEFAULT VALUE
a
NOTE(S):
a. Default value is shown only if configurable.
UNIT READ/WRITE
1 Vaporizer Heater On vphton 100 — RW
2 Vaporizer Heater Off vphtoff 120 — RW
3 Sump1 Heater On smp1on 140 — RW
4 Sump1 Heater Off smp1off 145 — RW
5 Sump2 Heater On smp2on 125 — RW
6 Sump2 Heater Off smp2off 140 — RW
7 Turn On HGBP hgbpon 200 — RW
8 Turn Off HGBP hgbpoff 5 — RW
9 Minimum Lift minlift 200 — RW
10 Minimum Hz minhz 24 — RW
RW — Read/Write
Hydronics Configuration
CCN TABLE NAME: HYDRCFG
PIC6 PATH: Main Menu Configuration Menu Hydronics Config