CMPA1CTL_isRd2St BV 92 Type 4 0 RO CmpA Ready to Stop
CMPA1CTL_isStart BV 93 Type 4 0 RO CmpA Started
CMPA1CTL_isStop BV 94 Type 4 0 RO CmpA Stopped
CMPA1CTL_iTS AV 199 Type 6 0 RO CmpA Inverter Temp Setpt
CMPA1CTL_mTS AV 200 Type 6 0 RO CmpA Motor Temp Setpt
CMPA1CTL_oVS AV 201 Type 6 0 RO CmpA Oil Viscosity Setpt
CMPA1CTL_rTS AV 202 Type 6 0 RO CmpA RectifierTemp Setpt
CMPA1CTL_shrt_cyc BV 95 Type 4 0 RO CmpA Short Cycle Prevent
CMPA1CTL_sSTS AV 203 Type 6 0 RO CmpA Sat Suct Temp Setpt
CMPA1CTL_stall_ct AV 204 Type 6 0 RO CmpA Stall Count
CMPA1CTL_statwrd AV 192 Type 6 0 RO CmpA State Diag Word
CMPA1CTL_vi_cmd BV 96 Type 4 0 RO CmpA Vi Command
CMPA1CTL_vi_cObj AV 209 Type 6 0 RO CmpA Vi Curr Objective
CMPA1CTL_vi_dword AV 210 Type 6 0 RO CmpA Vi Diag Word
CMPA1CTL_vi_sp1 AV 207 Type 6 0 RO CmpA Vi Stpt 1
CMPA1CTL_vi_sp2 AV 208 Type 6 0 RO CmpA Vi Stpt 2
CPMPCTL_disc_cmd BV 123 Type 4 0 RO Cond Pump Cmd
CPMPCTL_dWd AV 290 Type 6 0 RO Diagnostic Word
CPMPCTL_fWd AV 291 Type 6 0 RO Fault Word
CPMPCTL_has_flo BV 55 Type 4 0 RO Flow Established
CPMPCTL_isEnable BV 124 Type 4 0 RO Enable
CPMPCTL_isNom BV 125 Type 4 0 RO Nominal
CPMPCTL_isRd2Go BV 126 Type 4 0 RO Ready to Start
CPMPCTL_isRd2St BV 127 Type 4 0 RO Ready to Stop
CPMPCTL_isStart BV 128 Type 4 0 RO Started
CPMPCTL_isStop BV 129 Type 4 0 RO Stopped
CTLSTATE_ice_bld AV 38 Type 6 0 RO Ice Building
DRVA1CFG_curr_lim AV 396 Type 6 0 RW Current Limit Percent
DRVA1CFG_min_spd AV 393 Type 6 0 RW Compressor Unload Spd
DRVA1CFG_pwm_freq AV 397 Type 6 0 RW PWM Switch Frequency
DRVA1CFG_ramp_dec AV 403 Type 6 0 RW Decrease Ramp Time
DRVA1CFG_ramp_inc AV 402 Type 6 0 RW Increase Ramp Time
DRVA1CFG_rla AV 389 Type 6 0 RW Motor Nameplate Current
DRVA1CFG_rla_m AV 387 Type 6 0 RW Motor Rated Load Amps
DRVA1CFG_rlhz AV 392 Type 6 0 RW Compressor 100% Speed
DRVA1CFG_rlkw AV 391 Type 6 0 RW Motor Nameplate KW
DRVA1CFG_rlrpm AV 390 Type 6 0 RW Motor Nameplate RPM
DRVA1CFG_rlv AV 388 Type 6 0 RW Motor Nameplate Voltage
DRVA1CFG_rlv_i AV 386 Type 6 0 RW Rated Line Voltage
DRVA1CFG_skipband AV 401 Type 6 0 RW Skip Frequency Band
DRVA1CFG_skipfrq1 AV 398 Type 6 0 RW Skip Frequency 1
DRVA1CFG_skipfrq2 AV 399 Type 6 0 RW Skip Frequency 2
DRVA1CFG_skipfrq3 AV 400 Type 6 0 RW Skip Frequency 3
DRVA1CFG_strt_spd AV 394 Type 6 0 RW Compressor Start Spd
DRVA1CFG_torq_lim AV 395 Type 6 0 RW Torque Limit Percent
DRVA1STS_ALM_WD1 AV 174 Type 6 0 RO VFD Alarm Word1
DRVA1STS_ALM_WD2 AV 175 Type 6 0 RO VFD Alarm Word2
DRVA1STS_ALT_WD1 AV 172 Type 6 0 RO VFD Alert Word1
DRVA1STS_ALT_WD2 AV 173 Type 6 0 RO VFD Alert Word2
DRVA1STS_AMPS_PCT AV 161 Type 6 0 RO VFD Motor Curr Pct Rated
DRVA1STS_BUS_V AV 159 Type 6 0 RO VFD Bus Voltage
DRVA1STS_COMS MV 8 Type 5 0 RO VFD Coms Status
DRVA1STS_IGBT_T AV 166 Type 6 0 RO VFD IGBT Temp
DRVA1STS_INV_T AV 165 Type 6 0 RO VFD Inverter Temp
DRVA1STS_LAST_FLT AV 169 Type 6 0 RO VFD Last Fault Code
DRVA1STS_LINE_CUR AV 157 Type 6 0 RO VFD Average Line Current
DRVA1STS_LINE_KW AV 158 Type 6 0 RO VFD Average Line KW
DRVA1STS_LINE_V AV 156 Type 6 0 RO VFD Average Line Voltage
DRVA1STS_MOT_CUR AV 160 Type 6 0 RO VFD Motor Current
DRVA1STS_MOT_KW AV 162 Type 6 0 RO VFD Motor KW
DRVA1STS_MOT_RPM AV 168 Type 6 0 RO VFD Motor Rpm
DRVA1STS_PCT AV 163 Type 6 0 RO VFD Capacity
DRVA1STS_RECT_T AV 167 Type 6 0 RO VFD Rectifier Temp
DRVA1STS_SPD AV 164 Type 6 0 RO VFD Speed
DRVA1STS_STAT_WD1 AV 170 Type 6 0 RO VFD Status Word1
DRVA1STS_STAT_WD2 AV 171 Type 6 0 RO VFD Status Word2
ECOACTL_cObj AV 226 Type 6 0 RO Current Objective
APPENDIX C — NETWORK CONFIGURATION (cont)
BACnet Points List (cont)
OBJECT NAME TYPE INSTANCE OPTION COVINC PV ACCESS DESCRIPTION