FACTORY_exv_opt MV 14 Type 5 0 RW EXV Control Type
FACTORY_hgbp_opt BV 159 Type 4 0 RW HGBP Control Option
FACTORY_oilassy AV 367 Type 6 0 RW Oil Assembly Option
FACTORY_refrig MV 12 Type 5 0 RW Refrigerant Type
FACTORY_tons AV 365 Type 6 0 RW Chiller Tons
FACTORY_vfd_opt MV 13 Type 5 0 RW VFD Option
GENCONF_caplim_a AV 4 Type 6 0 RW Circuit A Capacity Limit
GENCONF_caplim_b AV 5 Type 6 0 RW Circuit B Capacity Limit
GENCONF_dem_sel MV 3 Type 5 0 RW Demand Limit Source
GENCONF_ice_rec BV 2 Type 4 0 RW Ice Mode Recycle
GENCONF_lead_ck MV 2 Type 5 0 RW Lead Circuit Selection
GENCONF_leak_en BV 3 Type 4 0 RW Refrigerant Leak Option
GENCONF_ramp_en BV 1 Type 4 0 RW Enable Ramp Loading
GENCONF_rampsel MV 1 Type 5 0 RW Ramp Loading Type
GENCONF_rrate_a AV 2 Type 6 0 RW Ramp Rate (per Min)
GENCONF_rrate_k AV 3 Type 6 0 RW Ramp Rate (per Min)
GENCONF_rrate_t AV 1 Type 6 0 RW Ramp Rate (per Min)
GENUNIT_BAC_OCC BV 4 Type 4 0 RO BACnet Occupied
GENUNIT_CHIL_S_S BV 6 Type 4 0 RO Cmd Start/Stop
GENUNIT_CTRL_PNT AV 35 Type 6 0 RO Control Point
GENUNIT_DEM_LIM AV 36 Type 6 0 RO Active Demand Limit
GENUNIT_EMSTOP BV 7 Type 4 0 RO Emergency Stop
GENUNIT_ICE_OCC BV 9 Type 4 0 RO Ice Build Occupied
GENUNIT_LAG_LIM AV 37 Type 6 0 RO Lag Demand Limit
GENUNIT_LCL_S_S BV 5 Type 4 0 RO HMI Start/Stop Cmd
GENUNIT_LOC_OCC BV 8 Type 4 0 RO Local Sched Occupied
GENUNIT_min_left AV 33 Type 6 0 RO Time Until Start
GENUNIT_min_run AV 34 Type 6 0 RO Minimum Runtime Timer
GENUNIT_ONOFFSVC MV 5 Type 5 0 RO Unit Mode
GENUNIT_ramp_act BV 10 Type 4 0 RO Ramp Loading Active
GENUNIT_ramprate AV 39 Type 6 0 RO Ramp Rate (per Min)
GENUNIT_rpdrstst MV 7 Type 5 0 RO Swift Restart State
GENUNIT_STATUS MV 4 Type 5 0 RO Unit Status
GENUNIT_SYS_STAT MV 6 Type 5 0 RO System State
HGBPACTL_cmd AV 233 Type 6 0 RO HGBPA Command
HGBPACTL_cObj AV 231 Type 6 0 RO HGBPA Current Obj
HGBPACTL_cSS AV 235 Type 6 0 RO HGBPA Comp Spd Stpt
HGBPACTL_do_cmd BV 110 Type 4 0 RO HGBPA Disc Out Cmd
HGBPACTL_dWd AV 237 Type 6 0 RO HGBPA Diag Word
HGBPACTL_fTS AV 234 Type 6 0 RO HGBPA Fluid T Stpt
HGBPACTL_fWd AV 238 Type 6 0 RO HGBPA Fault Word
HGBPACTL_hgbpa_pt AV 232 Type 6 0 RO HGBPA Process Temp
HGBPACTL_isEnable BV 111 Type 4 0 RO HGBPA Enable
HGBPACTL_isNom BV 112 Type 4 0 RO HGBPA Nominal
HGBPACTL_isRd2Go BV 113 Type 4 0 RO HGBPA Ready to Start
HGBPACTL_isRd2St BV 114 Type 4 0 RO HGBPA Ready to Stop
HGBPACTL_isStart BV 115 Type 4 0 RO HGBPA Started
HGBPACTL_isStop BV 116 Type 4 0 RO HGBPA Stopped
HGBPACTL_svPS AV 236 Type 6 0 RO HGBPA SV Pos Stpt
HYDRCFG_cflo_vt AV 385 Type 6 0 RW Cond Flow Verify time
HYDRCFG_condfdtp AV 383 Type 6 0 RW Cond Flow Detection Type
HYDRCFG_condfldp AV 384 Type 6 0 RW Cond Min Flow dP
HYDRCFG_eflo_vt AV 382 Type 6 0 RW Evap Flow Verify time
HYDRCFG_evapfdtp AV 380 Type 6 0 RW Evap Flow Detection Type
HYDRCFG_evapfldp AV 381 Type 6 0 RW Evap Min Flow dP
INPUTS_AUTO_DEM AV 127 Type 6 0 RO Auto Demand Limit Input
INPUTS_AUTO_RES AV 128 Type 6 0 RO Auto Water Temp Reset
INPUTS_CNDLVL_A AV 133 Type 6 0 RO Cond Liq Lev A
INPUTS_CNDLVL_B AV 136 Type 6 0 RO Cond Liq Lev B
INPUTS_COND_FSW BV 49 Type 4 0 RO Condenser Flow Switch
INPUTS_E_STOP BV 42 Type 4 0 RO Emergency Stop Contact
INPUTS_ECOA_FBK AV 131 Type 6 0 RO Econ A EXV Feedback
INPUTS_ECOB_FBK AV 135 Type 6 0 RO Econ B EXV Feedback
INPUTS_EVAP_FSW BV 50 Type 4 0 RO Evaporator Flow Switch
INPUTS_EXVA_FBK AV 130 Type 6 0 RO Main EXV A Feedback
INPUTS_EXVB_FBK AV 134 Type 6 0 RO Main EXV B Feedback
INPUTS_FS_LOCK BV 43 Type 4 0 RO Fire Security Interlock
APPENDIX C NETWORK CONFIGURATION (cont)
BACnet Points List (cont)
OBJECT NAME TYPE INSTANCE OPTION COVINC PV ACCESS DESCRIPTION