74
0x00D7 215 2 STRTSTS_sum2ht_h I2T Sum Heat Phase 2 FLOAT IR % 0
0x00D8 216 2 STRTSTS_sum3ht_h I2T Sum Heat Phase 3 FLOAT IR % 0
0x00D9 217 2 STRTSTS_KW Motor KW FLOAT IR kW 0
0x00DA 218 1 STRTSTS_start_ok 1CR Start Complete UINT IR 0 1 0
0x00DB 219 1 STRTSTS_stop_ok 1CR Stop Complete UINT IR 0 1 0
0x00DC 220 1 STRTSTS_cycle_1 Single Cycle Dropout UINT IR 0 1 0
0x00DD 221 1 STRTSTS_ph_loss Phase Loss UINT IR 0 1 0
0x00DE 222 1 STRTSTS_ov_volt Over Voltage UINT IR 0 1 0
0x00DF 223 1 STRTSTS_un_volt Under Voltage UINT IR 0 1 0
0x00E0 224 1 STRTSTS_amp_unb Current Imbalance UINT IR 0 1 0
0x00E1 225 1 STRTSTS_volt_unb Voltage Imbalance UINT IR 0 1 0
0x00E2 226 1 STRTSTS_overload Overload Trip UINT IR 0 1 0
0x00E3 227 1 STRTSTS_lratrip Locked Rotor Trip UINT IR 0 1 0
0x00E4 228 1 STRTSTS_slratrip Starter Lock Rotor Trip UINT IR 0 1 0
0x00E5 229 1 STRTSTS_grnd_flt Ground Fault UINT IR 0 1 0
0x00E6 230 1 STRTSTS_ph_rev Phase Reversal UINT IR 0 1 0
0x00E7 231 1 STRTSTS_freqflt Frequency Out of Range UINT IR 0 1 0
0x00E8 232 1 STRTSTS_ism_por ISM Power On Reset UINT IR 0 1 0
0x00E9 233 1 STRTSTS_m1_flt 1M Start/Run Fault UINT IR 0 1 0
0x00EA 234 1 STRTSTS_m2_flt 2M Start/Run Fault UINT IR 0 1 0
0x00EB 235 1 STRTSTS_prs_trip Pressure Trip Contact UINT IR 0 1 0
0x00EC 236 1 STRTSTS_strt_flt Starter Fault UINT IR 0 1 0
0x00ED 237 1 STRTSTS_no_amps Motor Amps Not Sensed UINT IR 0 1 0
0x00EE 238 1 STRTSTS_accelflt Starter Accel Fault UINT IR 0 1 0
0x00EF 239 1 STRTSTS_highamps Excessive Motor Amps UINT IR 0 1 0
0x00F0 240 1 STRTSTS_m1m2stop 1M/2M Stop Fault UINT IR 0 1 0
0x00F1 241 1 STRTSTS_ampstop Motor Amps When Stopped UINT IR 0 1 0
0x00F2 242 1 STRTSTS_hardware Hardware Failure UINT IR 0 1 0
0x00F3 243 1 STRTSTS_calfc_er Calibration Factor Error UINT IR 0 1 0
0x00F4 244 1 STRTSTS_conf_err Invalid Configuration UINT IR 0 1 0
0x00F5 245 1 DRVA1STS_COMS VFD Coms Status UINT IR 0 2 0
MV: 0=OK,
1=PARTIAL, 2=NO
COMS
0x00F7 247 2 DRVA1STS_LINE_V VFD Average Line Voltage FLOAT IR V 0
0x00F8 248 2 DRVA1STS_LINE_CUR VFD Average Line Current FLOAT IR amp 0
0x00F9 249 2 DRVA1STS_LINE_KW VFD Average Line KW FLOAT IR kW 0
0x00FA 250 2 DRVA1STS_BUS_V VFD Bus Voltage FLOAT IR V 0
0x00FB 251 2 DRVA1STS_MOT_CUR VFD Motor Current FLOAT IR amp 0
0x00FC 252 2 DRVA1STS_AMPS_PCT VFD Motor Curr Pct Rated FLOAT IR % 0
0x00FD 253 2 DRVA1STS_MOT_KW VFD Motor KW FLOAT IR kW 0
0x00FE 254 2 DRVA1STS_PCT VFD Capacity FLOAT IR % 0
0x00FF 255 2 DRVA1STS_SPD VFD Speed FLOAT IR Hz 0
0x0100 256 2 DRVA1STS_INV_T VFD Inverter Temp FLOAT IR
°F 0
°C –17.78
0x0101 257 2 DRVA1STS_IGBT_T VFD IGBT Temp FLOAT IR
°F 0
°C –17.78
0x0102 258 2 DRVA1STS_RECT_T VFD Rectifier Temp FLOAT IR
°F 0
°C –17.78
0x0103 259 2 DRVA1STS_MOT_RPM VFD Motor Rpm FLOAT IR rpm 0
0x0104 260 2 DRVA1STS_LAST_FLT VFD Last Fault Code FLOAT IR 0
0x0105 261 2 DRVA1STS_STAT_WD1 VFD Status Word1 FLOAT IR 0
0x0106 262 2 DRVA1STS_STAT_WD2 VFD Status Word2 FLOAT IR 0
0x0107 263 2 DRVA1STS_ALT_WD1 VFD Alert Word1 FLOAT IR 0
0x0108 264 2 DRVA1STS_ALT_WD2 VFD Alert Word2 FLOAT IR 0
0x0109 265 2 DRVA1STS_ALM_WD1 VFD Alarm Word1 FLOAT IR 0
0x010A 266 2 DRVA1STS_ALM_WD2 VFD Alarm Word2 FLOAT IR 0
0x010B 267 1 STGECTL_cmp1cknb Cmp 1 Circ Num UINT IR 0
0x010C 268 1 STGECTL_cmp1hgbp Cmp 1 HGBP UINT IR 0 1 0
0x010D 269 1 STGECTL_cmp1ldrq Cmp1 Load Required UINT IR 0
0x010E 270 1 STGECTL_comp_ld Cmp Load UINT IR 0 1 0
0x010F 271 1 STGECTL_comp_ul Cmp Unload UINT IR 0 1 0
0x0110 272 1 STGECTL_ld_alwd Loading Allowed UINT IR 0 1 0
0x0111 273 1 STGECTL_leadck Lead Circ Num UINT IR 0
0x0112 274 1 STGECTL_stat_wrd Stage Status Word UINT IR 0
0x0114 276 1 STGECTL_ul_alwd Unloading Allowed UINT IR 0 1 0
0x0115 277 2 CMPA1CTL_aDSTMn CmpA AbsDischSatTMin FLOAT IR 0
0x0116 278 2 CMPA1CTL_aDSTMx CmpA AbsDischSatTMax FLOAT IR 0
0x0117 279 2 CMPA1CTL_aSSTMn CmpA AbsSuctSat TMin FLOAT IR 0
APPENDIX D — MODBUS CONFIGURATION
a
(cont)
ADDRESS
REG. PARAMETER DESCRIPTION
DISPLAY
MODE
(16BITS)
TYPE UNIT
VALUE
COMMENT
HEXADEC. DEC. MIN. MAX. DEFAULT