49
30RAP ELECTRICAL DATA (cont)
DUAL POINT HYDRONIC PACKAGE WITH STANDARD LOW-SOUND AEROACOUSTIC™ FAN
LEGEND
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit terminals
is not below or above the listed minimum and maximum limits. Maximum allowable phase
imbalance is: voltage, 2%; amps 10%.
2. All units/modules have dual point primary power connection. (Each unit/module requires its
own power supply.) Main power must be supplied from a field-supplied disconnect.
3. Cooler heater is wired into the control circuit so it is always operable as long as the power
supply disconnect is on, even if any safety device is open.
4. Power draw control circuits include cooler heaters (where used).
38RAP UNIT
SIZE
VOLTAGE
V-Hz (3 Ph )
PUMP SIZE 3.0 hp PUMP SIZE 3.0 hp
CIRCUIT 1 CIRCUIT 2
MCA MOCP ICF REC FUSE MCA MOCP ICF REC FUSE
070
208/230-3-60 155.6 200 425.8 175 192.2 225 462.4 225
380-3-60 96.0 125 249.5 110 116.4 150 269.9 125
460-3-60 75.0 100 220.4 90 92.3 110 237.7 100
575-3-60 65.3 80 167.7 80 80.9 100 183.3 90
080
208/230-3-60 — — — — — — — —
380-3-60 — — — — — — — —
460-3-60 — — — — — — — —
575-3-60 — — — — — — — —
090
208/230-3-60 — — — — — — — —
380-3-60 — — — — — — — —
460-3-60 — — — — — — — —
575-3-60 — — — — — — — —
38RAP UNIT
SIZE
VOLTAGE
V-Hz (3 Ph )
PUMP SIZE 5.0 hp PUMP SIZE 5.0 hp
CIRCUIT 1 CIRCUIT 2
MCA MOCP ICF REC FUSE MCA MOCP ICF REC FUSE
070
208/230-3-60 155.6 200 425.8 175 199.1 250 469.3 225
380-3-60 96.0 125 249.5 110 120.2 150 273.7 150
460-3-60 75.0 100 220.4 90 95.4 110 240.8 110
575-3-60 65.3 80 167.7 80 83.4 100 185.8 90
080
208/230-3-60 202.7 250 438.6 225 199.1 250 469.3 225
380-3-60 110.8 125 216.2 125 120.2 150 273.7 150
460-3-60 92.5 110 213.6 100 95.4 110 240.8 110
575-3-60 79.1 90 163.2 90 83.4 100 185.8 90
090
208/230-3-60 217.4 250 487.6 250 199.1 250 469.3 225
380-3-60 133.9 150 287.4 150 120.2 150 273.7 150
460-3-60 104.8 125 250.2 125 95.4 110 240.8 110
575-3-60 91.4 110 193.8 100 83.4 100 185.8 90
38RAP UNIT
SIZE
VOLTAGE
V-Hz (3 Ph )
PUMP SIZE 7.5 hp PUMP SIZE 7.5 hp
CIRCUIT 1 CIRCUIT 2
MCA MOCP ICF REC FUSE MCA MOCP ICF REC FUSE
070
208/230-3-60 155.6 200 425.8 175 207.1 250 477.3 225
380-3-60 96.0 125 249.5 110 124.5 150 278.0 150
460-3-60 75.0 100 220.4 90 99.0 110 244.4 110
575-3-60 65.3 80 167.7 80 86.3 100 188.7 100
080
208/230-3-60 202.7 250 438.6 225 207.1 250 477.3 225
380-3-60 110.8 125 216.2 125 124.5 150 278.0 150
460-3-60 92.5 110 213.6 100 99.0 110 244.4 110
575-3-60 79.1 90 163.2 90 86.3 100 188.7 100
090
208/230-3-60 217.4 250 487.6 250 207.1 250 477.3 225
380-3-60 133.9 150 287.4 150 124.5 150 278.0 150
460-3-60 104.8 125 250.2 125 99.0 110 244.4 110
575-3-60 91.4 110 193.8 100 86.3 100 188.7 100
38RAP UNIT
SIZE
VOLTAGE
V-Hz (3 Ph )
PUMP SIZE 10.0 hp PUMP SIZE 10.0 hp
CIRCUIT 1 CIRCUIT 2
MCA MOCP ICF REC FUSE MCA MOCP ICF REC FUSE
070
208/230-3-60 155.6 200 425.8 175 215.0 250 485.2 250
380-3-60 96.0 125 249.5 110 128.9 150 282.4 150
460-3-60 75.0 100 220.4 90 102.6 110 248.0 110
575-3-60 65.3 80 167.7 80 89.2 100 191.6 100
080
208/230-3-60 202.7 250 438.6 225 215.0 250 485.2 250
380-3-60 110.8 125 216.2 125 128.9 150 282.4 150
460-3-60 92.5 110 213.6 100 102.6 110 248.0 110
575-3-60 79.1 90 163.2 90 89.2 100 191.6 100
090
208/230-3-60 217.4 250 487.6 250 215.0 250 485.2 250
380-3-60 133.9 150 287.4 150 128.9 150 282.4 150
460-3-60 104.8 125 250.2 125 102.6 110 248.0 110
575-3-60 91.4 110 193.8 100 89.2 100 191.6 100
38RAP UNIT
SIZE
VOLTAGE
V-Hz (3 Ph )
PUMP SIZE 15.0 hp PUMP SIZE 15.0 hp
CIRCUIT 1 CIRCUIT 2
MCA MOCP ICF REC FUSE MCA MOCP ICF REC FUSE
070
208/230-3-60 — — — — — — — —
380-3-60 — — — — — — — —
460-3-60 — — — — — — — —
575-3-60 — — — — — — — —
080
208/230-3-60 202.7 250 438.6 225 231.2 250 501.4 250
380-3-60 110.8 125 216.2 125 137.7 150 291.2 150
460-3-60 92.5 110 213.6 100 109.9 110 255.3 110
575-3-60 79.1 90 163.2 90 95.0 100 197.4 100
090
208/230-3-60 217.4 250 487.6 250 231.2 250 501.4 250
380-3-60 133.9 150 287.4 150 137.7 150 291.2 150
460-3-60 104.8 125 250.2 125 109.9 110 255.3 110
575-3-60 91.4 110 193.8 100 95.0 100 197.4 100
ICF — Instantaneous Current Flow
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection