30RAP ELECTRICAL DATA
DUAL POINT LOW SOUND AEROACOUSTIC™ FAN NO HYDRONIC PACKAGE
30RAP ELECTRICAL DATA
DUAL POINT OPTIONAL VALUE SOUND FAN NO HYDRONIC PACKAGE
LEGEND
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit terminals
is not below or above the listed minimum and maximum limits. Maximum allowable phase
imbalance is: voltage, 2%; amps 10%.
2. All units/modules have dual point primary power connection. (Each unit/module requires its
own power supply.) Main power must be supplied from a field-supplied disconnect.
3. Cooler heater is wired into the control circuit so it is always operable as long as the power
supply disconnect is on, even if any safety device is open.
4. Power draw control circuits include cooler heaters (where used).
UNIT
30RAP
UNIT VOLTAGE CIRCUIT 1 CIRCUIT 2
V-Hz
(3 Ph)
Supplied
MCA MOCP ICF
Rec
Fuse
Size
MCA MOCP ICF
Rec
Fuse
Size
Min Max
070
208/230-3-60 187 254 155.6 200 425.8 175 181.4 225 451.6 200
380-3-60 342 418 96.0 125 249.5 110 110.5 125 264.0 125
460-3-60 414 506 75.0 100 220.4 90 87.4 110 232.8 100
575-3-60 518 632 65.3 80 167.7 80 77.0 100 179.4 90
080
208/230-3-60 187 254 202.7 250 438.6 225 181.4 225 451.6 200
380-3-60 342 418 110.8 125 216.2 125 110.5 125 264.0 125
460-3-60 414 506 92.5 110 213.6 100 87.4 110 232.8 100
575-3-60 518 632 79.1 90 163.2 90 77.0 100 179.4 90
090
208/230-3-60 187 254 217.4 250 487.6 250 181.4 225 451.6 200
380-3-60 342 418 133.9 150 287.4 150 110.5 125 264.0 125
460-3-60 414 506 104.8 125 250.2 125 87.4 110 232.8 100
575-3-60 518 632 91.4 110 193.8 100 77.0 100 179.4 90
UNIT
30RAP
UNIT VOLTAGE CIRCUIT 1 CIRCUIT 2
V-Hz
(3 Ph)
Supplied
MCA MOCP ICF
Rec
Fuse
Size
MCA MOCP ICF
Rec
Fuse
Size
Min Max
070
208/230-3-60 187 254 158.6 200 428.8 175 181.4 225 451.6 200
380-3-60 342 418 96.0 125 249.5 110 110.5 125 264.0 125
460-3-60 414 506 77.0 100 222.4 90 87.4 110 232.8 100
575-3-60 518 632 66.3 90 168.7 80 77.0 100 179.4 90
080
208/230-3-60 187 254 206.3 250 442.2 225 181.4 225 451.6 200
380-3-60 342 418 110.8 125 216.2 125 110.5 125 264.0 125
460-3-60 414 506 94.9 110 216.0 110 87.4 110 232.8 100
575-3-60 518 632 80.3 100 164.4 90 77.0 100 179.4 90
090
208/230-3-60 187 254 221.0 250 491.2 250 181.4 225 451.6 200
380-3-60 342 418 133.9 150 287.4 150 110.5 125 264.0 125
460-3-60 414 506 107.2 125 252.6 125 87.4 110 232.8 100
575-3-60 518 632 92.6 110 195.0 100 77.0 100 179.4 90
ICF — Instantaneous Current Flow
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
Electrical data (cont)