48
30RAP ELECTRICAL DATA (cont)
SINGLE POINT HYDRONIC PACKAGE WITH STANDARD LOW-SOUND AEROACOUSTIC™ FAN (cont)
LEGEND
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit terminals
is not below or above the listed minimum and maximum limits. Maximum allowable phase
imbalance is: voltage, 2%; amps 10%.
2. All units/modules have single point primary power connection. (Each unit/module requires
its own power supply.) Main power must be supplied from a field-supplied disconnect.
3. Cooler heater is wired into the control circuit so it is always operable as long as the power
supply disconnect is on, even if any safety device is open.
4. Power draw control circuits include cooler heaters (where used).
38RAP UNIT SIZE
VOLTAGE
V-Hz (3 Ph)
PUMP SIZE 7.5 hp PUMP SIZE 10.0 hp PUMP SIZE 15.0 hp
MCA MOCP ICF REC FUSE MCA MOCP ICF REC FUSE MCA MOCP ICF REC FUSE
010
208/230-60 — — — — — — — — — — — —
380-60 ————————————
460-60 ————————————
575-60 ————————————
015
208/230-60 — — — — — — — — — — — —
380-60 ————————————
460-60 ————————————
575-60 ————————————
018
208/230-60 — — — — — — — — — — — —
380-60 ————————————
460-60 ————————————
575-60 ————————————
020
208/230-60 — — — — — — — — — — — —
380-60 ————————————
460-60 ————————————
575-60 ————————————
025
208/230-60 — — — — — — — — — — — —
380-60 ————————————
460-60 ————————————
575-60 ————————————
030
208/230-60 — — — — — — — — — — — —
380-60 ————————————
460-60 ————————————
575-60 ————————————
035
208/230-60 183.9 200 378.1 200 — — — — — — — —
380-60 113.9 125 229.3 125 — — — — — — — —
460-60 91.1 100 193.7 100 — — — — — — — —
575-60 73.1 80 135.2 80 — — — — — — — —
040
208/230-60 216.3 250 413.5 250 — — — — — — — —
380-60 122.9 125 238.2 125 — — — — — — — —
460-60 95.1 110 197.5 100 — — — — — — — —
575-60 75.9 90 157.9 80 — — — — — — — —
045
208/230-60 248.1 250 487.2 250 — — — — — — — —
380-60 130.0 150 238.6 150 — — — — — — — —
460-60 106.6 125 232.2 125 — — — — — — — —
575-60 88.4 100 177.7 100 — — — — — — — —
050
208/230-60 254.5 300 490.4 300 261.0 300 496.9 300 — — — —
380-60 136.4 150 241.8 150 140.0 150 245.4 150 — — — —
460-60 115.6 125 236.7 125 118.4 125 239.5 125 — — — —
575-60 98.8 110 182.9 110 101.0 110 185.1 110 — — — —
055
208/230-60 270.7 300 545.4 300 277.2 300 551.9 300 — — — —
380-60 156.3 175 316.9 175 159.9 175 320.5 175 — — — —
460-60 127.0 150 276.2 150 129.8 150 279.0 150 — — — —
575-60 109.7 125 215.9 125 111.9 125 218.1 125 — — — —
060
208/230-60 279.7 300 549.9 300 286.2 300 556.4 300 — — — —
380-60 170.5 200 324.0 200 174.1 200 327.6 200 — — — —
460-60 134.6 150 280.0 150 137.4 150 282.8 150 — — — —
575-60 117.3 125 219.7 125 119.5 125 221.9 125 — — — —
070
208/230-60 348.7 400 618.9 400 356.6 400 626.8 400 — — — —
380-60 212.0 225 365.5 225 216.4 250 369.9 225 — — — —
460-60 167.3 175 312.7 175 170.9 175 316.3 175 — — — —
575-60 145.7 150 248.1 150 148.6 150 251.0 150 — — — —
080
208/230-60 397.0 450 667.2 450 404.9 450 675.1 450 421.1 450 691.3 450
380-60 228.6 250 382.1 250 233.0 250 386.5 250 241.8 250 395.3 250
460-60 185.7 200 331.1 200 189.3 200 334.7 200 196.6 200 342.0 200
575-60 160.4 175 262.8 175 163.3 175 265.7 175 169.1 175 271.5 175
090
208/230-60 410.5 450 680.7 450 418.4 450 688.6 450 434.6 450 704.8 450
380-60 249.9 250 403.4 250 254.3 300 407.8 300 263.1 300 416.6 300
460-60 197.1 200 342.5 200 200.7 225 346.1 225 208.0 225 353.4 225
575-60 171.8 175 274.2 175 174.7 175 277.1 175 180.5 200 282.9 200
ICF — Instantaneous Current Flow
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
Electrical data (cont)