51
30RAP ELECTRICAL DATA (cont)
SINGLE POINT HYDRONIC PACKAGE WITH OPTIONAL VALUE SOUND FANS (cont)
LEGEND
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit terminals
is not below or above the listed minimum and maximum limits. Maximum allowable phase
imbalance is: voltage, 2%; amps 10%.
2. All units/modules have single point primary power connection. (Each unit/module requires
its own power supply.) Main power must be supplied from a field-supplied disconnect.
3. Cooler heater is wired into the control circuit so it is always operable as long as the power
supply disconnect is on, even if any safety device is open.
4. Power draw control circuits include cooler heaters (where used).
38RAP UNIT SIZE
VOLTAGE
V-Hz (3 Ph)
PUMP SIZE 7.5 hp PUMP SIZE 10.0 hp PUMP SIZE 15.0 hp
MCA MOCP ICF REC FUSE MCA MOCP ICF REC FUSE MCA MOCP ICF REC FUSE
010
208/230-60 — — — — — — — — — — — —
380-60 — — — — — — — — — — — —
460-60 — — — — — — — — — — — —
575-60 — — — — — — — — — — — —
015
208/230-60 — — — — — — — — — — — —
380-60 — — — — — — — — — — — —
460-60 — — — — — — — — — — — —
575-60 — — — — — — — — — — — —
018
208/230-60 — — — — — — — — — — — —
380-60 — — — — — — — — — — — —
460-60 — — — — — — — — — — — —
575-60 — — — — — — — — — — — —
020
208/230-60 — — — — — — — — — — — —
380-60 — — — — — — — — — — — —
460-60 — — — — — — — — — — — —
575-60 — — — — — — — — — — — —
025
208/230-60 — — — — — — — — — — — —
380-60 — — — — — — — — — — — —
460-60 — — — — — — — — — — — —
575-60 — — — — — — — — — — — —
030
208/230-60 — — — — — — — — — — — —
380-60 — — — — — — — — — — — —
460-60 — — — — — — — — — — — —
575-60 — — — — — — — — — — — —
035
208/230-60 185.7 200 379.9 200 — — — — — — — —
380-60 113.9 125 229.3 125 — — — — — — — —
460-60 92.3 110 194.9 100 — — — — — — — —
575-60 73.7 80 135.8 80 — — — — — — — —
040
208/230-60 218.1 250 415.3 250 — — — — — — — —
380-60 122.9 125 238.2 125 — — — — — — — —
460-60 96.3 110 198.7 110 — — — — — — — —
575-60 76.5 90 158.5 90 — — — — — — — —
045
208/230-60 249.9 300 489.0 300 — — — — — — — —
380-60 130.0 150 238.6 150 — — — — — — — —
460-60 107.8 125 233.4 125 — — — — — — — —
575-60 89.0 100 178.3 100 — — — — — — — —
050
208/230-60 256.3 300 492.2 300 262.8 300 498.7 300 — — — —
380-60 136.4 150 241.8 150 140.0 150 245.4 150 — — — —
460-60 116.8 125 237.9 125 119.6 125 240.7 125 — — — —
575-60 99.4 110 183.5 110 101.6 110 185.7 110 — — — —
055
208/230-60 273.1 300 547.8 300 279.6 300 554.3 300 — — — —
380-60 156.3 175 316.9 175 159.9 175 320.5 175 — — — —
460-60 128.6 150 277.8 150 131.4 150 280.6 150 — — — —
575-60 110.5 125 216.7 125 112.7 125 218.9 125 — — — —
060
208/230-60 282.1 300 552.3 300 288.6 300 558.8 300 — — — —
380-60 170.5 200 324.0 200 174.1 200 327.6 200 — — — —
460-60 136.2 150 281.6 150 139.0 150 284.4 150 — — — —
575-60 118.1 125 220.5 125 120.3 125 222.7 125 — — — —
070
208/230-60 351.7 400 621.9 400 359.6 400 629.8 400 — — — —
380-60 212.0 225 365.5 225 216.4 250 369.9 225 — — — —
460-60 169.3 175 314.7 175 172.9 175 318.3 175 — — — —
575-60 146.7 150 249.1 150 149.6 150 252.0 150 — — — —
080
208/230-60 400.6 450 670.8 450 408.5 450 678.7 450 424.7 450 694.9 450
380-60 228.6 250 382.1 250 233.0 250 386.5 250 241.8 250 395.3 250
460-60 188.1 200 333.5 200 191.7 200 337.1 200 199.0 225 344.4 225
575-60 161.6 175 264.0 175 164.5 175 266.9 175 170.3 175 272.7 175
090
208/230-60 414.1 450 684.3 450 422.0 450 692.2 450 438.2 450 708.4 450
380-60 249.9 250 403.4 250 254.3 300 407.8 300 263.1 300 416.6 300
460-60 199.5 225 344.9 225 203.1 225 348.5 225 210.4 225 355.8 225
575-60 173.0 175 275.4 175 175.9 200 278.3 200 181.7 200 284.1 200
ICF — Instantaneous Current Flow
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection