EasyManua.ls Logo

Carrier Aquazone 50HQP Series - Page 19

Carrier Aquazone 50HQP Series
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
19
Fig. 17 — VFD Input and Output Power Connections, 50HQP Units
Table 2 — 50HQP072-242 Electrical Data
50HQP UNIT
SIZE
VOLTAGE
(V-Ph-Hz)
COMPRESSOR (x2) BLOWER MOTOR
MIN CIRCUIT
AMPS
MAX FUSE/
HACR
RLA LRA QTY FLA HP
072
208/230-1-60 16.7 79.0 1 7.0 1 44.6 60
208/230-3-60 10.4 73.0 1 3.6 1 27.0 35
460-3-60 5.8 38.0 1 1.8 1 14.9 20
096
208/230-1-60 19.6 130.0 1 9.8 2 53.9 70
208/230-3-60 13.7 83.0 1 6.2 2 37.0 50
460-3-60 6.2 41.0 1 3.1 2 17.1 20
575-3-60 4.8 33.0 1 2.6 2 13.4 15
120
208/230-1-60 26.3 134.0 1 9.8 2 69.0 90
208/230-3-60 15.6 110.0 1 8.0 3 43.1 50
460-3-60 7.8 52.0 1 3.9 3 21.
5 25
575-3-60 5.8 38.9 1 3.7 3 16.8 20
150
208/230-3-60 19.2 136.0 1 9.2 3 52.4 70
460-3-60 8.7 66.1 1 4.3 3 23.9 30
575-3-60 6.9 55.3 1 3.7 3 19.2 25
180
208/230-3-60 22.4 149.0 2 6.2 2 62.8 80
460-3-60 10.6 75.0 2 3.1 2 30.1 40
575-3-60 7.7 54.0 2 2.6 2 22.5 30
242
208/230-3-60 30.1 225.0 2 3.9 2 75.5 100
460-3-60 16.7 114.0 2 3.1 2 43.8 60
575-3-60 12.2 80.0 2 2.6 2 32.7 40

Table of Contents

Related product manuals