5
LEGEND
* 300 psig when unit is built with the 2-way solenoid valve option.
Table 2 — Physical Data — 50PCH,PCV (036-070) Units
50PCH,PCV UNIT
036 041 042 048 060 070
Cu CuNi Cu CuNi Cu CuNi Cu CuNi Cu CuNi Cu CuNi
COMPRESSOR (1 each) Scroll
Maximum Water Working Pressure (psig) 400*
PSC FAN MOTOR AND BLOWER
Fan Motor Type PSC
Fan Motor (hp)
1
/
2
3
/
4
1
/
2
3
/
4
Blower Wheel Size (Dia x W) (in.) 9 x 7 10 x 8 10 x 9 11 x 9
ECM FAN MOTOR AND BLOWER
Fan Motor Type/Speeds C.T. ECM
Fan Motor (hp)
1
/
2
3
/
4
1
Blower Wheel Size (Dia x W) (in.) 9 x 7 10 x 8 11 x 9
WATER CONNECTION SIZE
FPT (in.)
3
/
4
1
Coaxial Coil Volume (gal) 0.27 0.49 0.62
VERTICAL CABINET
Refrigeration Charge (oz) Cu: 44
Cu/Ni: 40
38 Cu: 43
Cu/Ni: 39
52 59 64
Air Coil Dimensions (H x W) 24 x 20.2 20 x 16 24 x 20.2 24 x 26.75 32 x 26.2
Std. Filter - 1 in. Throwaway (L x H) 24 x 24 20 x 20 24 x 24 24 x 30 16 x 30 (2)
Opt. Filter - 2 in. MERV 8 or 13 Throwaway
(L x H)
24 x 24 20 x 20 24 x 24 24 x 30 16 x 30 (2)
Weight - Operating (lb) 229 217 239 287 307 336
Weight - Shipping (lb)
255 243 265 312 331 360
HORIZONTAL CABINET
Refrigeration Charge (oz) 40
N/A
Cu: 43
Cu/Ni: 39
51 62 61
Air Coil Dimensions (H x W) 18 x 27.5 18 x 27.5 20 x 32 20 X 42
Std. Filter - 1 in. Throwaway (L x H) 18 x 30 18 x 30 20 x 34.5 20 x 24 (2)
Opt. Filter - 2 in. MERV 8 or 13 Throwaway
(L x H)
18 x 30 18 x 30 20 x 34.5 20 x 24 (2)
Weight - Operating (lb) 226 231 274 288 316
Weight - Shipping (lb) 270 264 299 318 365
CT — Constant Torque
ECM — Electronically Commutated Motor
FPT — Female Pipe Thread
PSC — Permanent Split Capacitor