W
weberkristineJul 31, 2025
How to troubleshoot a Carrier AQUAZONE 50PEC09-18 Heat Pump that won't turn on?
- BBrandon WoodJul 31, 2025
If your Carrier Heat Pump isn't running, first ensure the power supply is on and the disconnect is closed. Check for blown fuses and replace them or reset the circuit breaker, ensuring you use the correct fuses. If the voltage supply is below the minimum specified on the unit's data plate, contact your local power company. For thermostat issues, set the fan to 'ON' to see if it runs. Test the 'COOL' and 'HEAT' settings at their extremes to see if the unit responds in either mode. If nothing happens, the thermostat may be miswired or faulty. Verify 24 volts at the low voltage terminal strip between 'R' and 'C,' 'Y' and 'C,' and 'O' and 'C' on the condensing section. Also, check for 24 volts between terminals 'G' and 'C' in the air handler. Replace the thermostat if it's defective.