EasyManua.ls Logo

Carrier Bryant Payne day and night 585A/YAC - Cooling Troubleshooting Guide

Carrier Bryant Payne day and night 585A/YAC
14 pages
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TABLE
IX—COOLING
SERVICE
ANALYSIS
CHART
SYMPTOM
CAUSE
REMEDY
Compressor
and
condenser
fan
will
not
start.
Power
failure
Cal!
power
company.
Fuse
blown
or
circuit
breaker
tripped
Replace
fuse
or
reset
circuit
breaker.
Defective
thermostat,
contactor,
transformer,
or
control
relay
Replace
component.
Insufficient
line
voltage
Determine
cause
and
correct.
Incorrect
or
faulty
wiring
Check
wiring
diagram
and
rewire
correctly.
Thermostat
setting
too
high
Lower
thermostat
setting
below
room
temperature.
Compressor
will
not
start
but
condenser
fan
runs.
Faulty
wiring
or
loose
connections
in
compressor
circuit
Check
wiring
and
repair
or
replace.
Compressor
motor
burned
out,
seized,
or
internal
overload
open
Determine
cause.
Replace
compressor.
Defective
run/start
capacitor,
overload,
start
relay
Determine
cause
and.
rep.lace.
One
leg
of
three-phase
power
dead
Replace
fuse
or
reset
circuit
breaker.
Determine
cause.
Compressor
cycles
(other
than
normally
satisfying
thermostat)
Refrigerant
overcharge
or
undercharge
Blow
refrigerant,
evacuate
system,
and
recharge
to
nameplate.
Defective
compressor
Replace
and
determine
cause.
Insufficient
line
voltage
Determine
cause
and
correct.
Blocked
condenser
Determine
cause
and
correct.
Defective
run/start
capacitor,
overload,
start
relay,
or
reset
relay
Determine
cause
and
replace.
Defective
thermostat
Replace
thermostat.
Faulty
condenser
fan
motor
or
capacitor
Replace.
Restriction
in
refrigerant
system
Locate
restriction
and
remove.
Compressor
operates
continuously.
Dirty
air
filter
Replace
filter.
Unit
undersized
for
load
Decrease
load
or
increase
unit
size.
Thermostat
set
too
low
|
Reset
thermostat.
Low
refrigerant
charge
Locate
leak,
repair,
and
recharge.
Leaking
valves
in
compressor
Replace
compressor.
Air
in
system
Blow
refrigerant,
evacuate
system,
and
recharge.
Condenser
coil
dirty
or
restricted
Clean
coil
or
remove
restriction.
Excessive
head
pressure
Dirty
air
filter
Replace
filter.
Dirty
condenser
coil
Clean
coil.
Refrigerant
overcharged
Purge
excess
refrigerant.
Air
in
system
Blow
refrigerant,
evacuate
system,
and
recharge.
Condenser
air
restricted
or
air
short
cycling
Determine
cause
and
correct.
Head
pressure
too
low
Low
refrigerant
charge
Check
for
leaks,
repair,
and
recharge.
Compressor
valves
leaking
Replace
compressor.
Restriction
in
liquid
line
Remove
restriction.
Excessive
suction
pressure
High
heat
load
Check
for
source
and
eliminate.
Compressor
valves
leaking
Replace
compressor.
Refrigerant
overcharged
Purge
excess
refrigerant.
Suction
pressure
too
low
Dirty
air
filter
Replace
filter.
Low
refrigerant
charge
Check
for
leaks,
repair,
and
recharge.
Metering
device
or
low
side
restricted
Remove
source
of
restriction.
Insufficient
evaporator
airflow
Increase
air
quantity.
Check
filter—replace
if
necessary.
Temperature
too
low
in
conditioned
area
Reset
thermostat.
Outdoor
ambient
below
65®F
Install
low-ambient
kit.
Filter-drier
restricted
Replace.
If
the
coils
are
coated
with
dirt
or
lint,
they
should
be
vacuumed
with
a
vacuum
cleaner’s
soft
brush
attachment.
Be
careful
not
to
bend
the
fins.
If
the
coils
are
coated
with
oil
or
grease,
they
may
be
cleaned
with
a
mild
detergent
and
water
solution.
Rinse
coils
with
clear
water.
Be
careful
not
to
splash
water
on
motors,
insulation,
wiring,
or
filters.
D.
Condensate
Drain
The
drain
pan
and
condensate
drain
should
be
checked
at
the
same
time
the
cooling
coils
are
checked.
Clean
the
drain
pan
and
condensate
drain
by
removing
any
foreign
matter
from
the
pan.
Flush
pan
and
drain
tube
with
clear
water.
If
the
drain
tube
is
restricted,
it
can
generally
be
cleared
with
high-pressure
water.
If
this
does
not
work,
try
a
“plumber’s
snake”
or
similar
probe
device.
E.
Evaporator
Blower
The
blower
should
be
inspected
at
least
once
each
year.
Re¬
move
caked-on
dirt
from
the
blower
wheel
and
housing
with
brush;
remove
grease
with
mild
solvent.
Make
sure
blower
is
centered
in
the
blower
housing.
F.
Condenser
Fan
The
condenser
fan
should
be
kept
free
of
all
obstructions
to
ensure
proper
cooling.
Do
not
set
articles
on
top
of
the
cool¬
ing
unit
that
could
possibly
interfere
with
the
airflow
of
the
fan.
WARNING:
Do
not
poke
sticks,
screwdrivers,
or
any
other
object
into
revolving
fan
blades—severe
bodily
injury
may
result.
The
required
fan
position
is
shown
in
Figure
3.
Adjust
the
fan
position
by
loosening
the
setscrews
and
moving
the
fan
up
or
down.
G.
Electrical
Controls
and
Wiring
With
power
disconnected
to
unit,
check
all
electrical
connec¬
tions
for
tightness.
Tighten
all
screws
on
connections.
If
any
smoky
or
burned
connections
are
noticed,
disassemble
tbe
connection,
clean
all
parts,
strip
wire,
and
reassemble
prop¬
erly
and
securely.
Electrical
controls
are
difficult
to
check
without
proper
instrumentation;
therefore,
reconnect
electrical
power
to
unit
and
observe
unit
through
one
com¬
plete
operating
cycle.
If
there
are
any
discrepancies
in
the
operating
cycle,
contact
your
Dealer
and
request
service.
H.
Refrigerant
Circuit
The
refrigerant
circuit
is
difiicult
to
check
for
leaks
without
proper
equipment.
Therefore,
if
low-cooling
performance
is
suspected,
contact
your
local
Dealer
for
service.
I.
Cleaning
the
Heating
Section
1.
Turn
off
power
to
main
disconnect
switch.
2.
Remove
control
access
panel.
3.
Turn
off
manual
gas
valve
and
pilot
gas
cock.
4.
Disconnect
pilot
and
escapement
tubing.
5.
Remove
burners.
6.
Remove
flue
baffle
retainer
and
vent
section
shelf.
7.
Remove
flue
baffle.
8.
Clean
passages
with
suitable
brush.
9.
Reassemble
by
reversing
above
procedure.
-
1
4
-

Related product manuals