6 - COMBUSTION AIR AND VENT PIPING
6.6 Condensate Piping
Use materials acceptable to authority having jurisdiction.
In absence of such authority:
PVC or CPVC per ASTM D1785/D2845 Cement or
primer per ASME D2564 or F493.
Attach PVC tee provided with boiler and eld sourced
piping to condensate drain at bottom of boiler. See
gure 6-1.
Slope condensate drain pipe minimum 1/4" per foot
(21mm/m) away from boiler.
• Use eld source condensate pump if boiler located
below disposal point.
Field source condensate neutralizing kit as required
by authority having jurisdiction or for environmentally
friendly condensate disposal.
FIGURE 6-1 Condensate Drain
Condensate Tee
( eld installed)
on condensate drain
pipe