EasyManua.ls Logo

Carrier BWMAAN000050 - Page 31

Carrier BWMAAN000050
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
31
9.4 Boiler Start-up and Operational Test
1. Verify air is purged from hydronic piping
2. System test pumps - verify each pump is opera-
tional
3. Verify gas piping
Con rm pressure test. See section 7.3.
Visually inspect piping to determine there are no
open ttings or ends, and all valves at unused
outlets are closed and plugged/capped.
Purge air from piping
Check piping and connections for leaks
immediately after gas is turned on. Shut off
gas supply and make necessary repairs if leaks
found.
4. Follow OPERATING INSTRUCTIONS to initiate boiler
operation. See section 10.
5. Inspect combustion air and vent piping. Verify pipe
is not leaking and terminations are unobstructed
and vent gas discharge is not a nuisance or hazard.
6. Verify boiler functions.
7. Inspect condensate disposal system. Verify
condensate ows adequately and is disposed
properly.
8. Check control module operation.
9. Check eld-sourced limits, low water cutoffs, etc.
per manufacturer's instructions.
9.5 Check Combustion
Natural Gas
1. Measure input. English units*
Turn off gas to all other appliances.
Use ½, 1 or 2 cu ft dial on gas meter. Measure
time required for one or more complete
revolutions. Measure time for 1-2 minutes.
Calculate input.
Input (MBH) =
3600 x cu ft
seconds
Example: Gas ow from
Meter = 2 cu ft
Measured time = 72 seconds
Rate (MBH) =
3600 x 2 cu ft
= 100 MBH
72 seconds
*Metric - See Glossary
** Most propane systems do not have gas ow meters.
2. Compare measured input to table. Adjust input rate
9 - START UP PROCEDURE
if needed using gure 9-3 below.
Size Minimum Maximum
050 45 51
075 65 76
100 90 102
150 140 153
200 185 204
Natural Gas and Propane
3. Measure CO
2
and compare to table. Adjust CO
2
if
needed using gure 9-3 below. See gure 9-4 for
combustion air analyzer port.
Gas
CO
2
CO
Min.
Max.
Natural Gas 8.5 9.5 <100ppm
Propane 10.0 11.0 <150ppm
Natural Gas only**
4.
Measure input. Compare to table above. Continue
to measure input and CO
2
until both measured
values are within range speci ed in tables.
Propane Gas
Most propane systems do not have ow meters.
1. Check CO
2
. Propane should be between 10% and
11.0%.
If CO
2
is low increase gas ow following gure
9-3.
If CO
2
is high decrease gas ow following gure
9-3.
To increase gas ow turn 'throttle' left or counter
clockwise .
To decrease gas ow turn 'throttle' right or
clockwise .
Limit adjustment to one turn and retest.
9-3 Gas Valve

Related product manuals