Table 15 Pressure Mode and Sub-Mode Directory
Table 16 Set Point Mode and Sub-Mode Directory
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
PRC.A DP.A XXX.X PSIG DISCHARGE PRESSURE
SP.A XXX.X PSIG SUCTION PRESSURE
ECN.A XXX.X PSIG ECONOMIZER PRESSURE
OP.A1 XXX.X PSIG A1 OIL PRESSURE
OP.A2 XXX.X PSIG A2 OIL PRESSURE
DO.A1 XXX.X PSI A1 OIL PRESSURE DIFF.
Equals oil pressure minus
Economizer pressure
DO.A2 XXX.X PSI A2 OIL PRESSURE DIFF.
Equals oil pressure minus
Economizer pressure
FD.A1 XXX.X PSI A1 OIL FILTER DIFF. PRESS
Equals discharge pressure
minus oil pressure
FD.A2 XXX.X PSI A2 OIL FILTER DIFF. PRESS
Equals discharge pressure
minus oil pressure
PS.A1 XX.X PSI CALCULATED OIL PRESS A1
CKT A oil pressure setpoint 1
(See notes for Table 32)
PS.A2 XX.X PSI CALCULATED OIL PRESS A2
CKT A oil pressure setpoint 2
(See notes for Table 32)
PRC.B DP.B XXX.X PSIG DISCHARGE PRESSURE
SP.B XXX.X PSIG SUCTION PRESSURE
ECN.B XXX.X PSIG ECONOMIZER PRESSURE
OP.B1 XXX.X PSIG B1 OIL PRESSURE
OP.B2 XXX.X PSIG B2 OIL PRESSURE
DO.B1 XXX.X PSI B1 OIL PRESSURE DIFF.
Equals oil pressure minus
Economizer pressure
DO.B2 XXX.X PSI B2 OIL PRESSURE DIFF.
Equals oil pressure minus
Economizer pressure
FD.B1 XXX.X PSI B1 OIL FILTER DIFF.
Equals discharge pressure
minus oil pressure
FD.B2 XXX.X PSI B2 OIL FILTER DIFF.
Equals discharge pressure
minus oil pressure
PS.B1 XX.X PSI CALCULATED OIL PRESS B1
CKT B oil pressure setpoint 1
(See notes for Table 32)
PS.B2 XX.X PSI CALCULATED OIL PRESS B2
CKT B oil pressure setpoint 2
(See notes for Table 32)
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
COOL CSP.1 XXX.X °F COOLING SETPOINT 1
Default: 44 F
CSP.2 XXX.X °F COOLING SETPOINT 2
Default: 44 F
CSP.3 XXX.X °F ICE SETPOINT
Default: 32 F
HEAT HSP.1 XXX.X °F HEATING SETPOINT 1
Default: 100 F
HSP.2 XXX.X °F HEATING SETPOINT 2
Default: 100 F
HEAD HD.P.A XXX.X °F HEAD PRESSURE SETPOINT A
Default: 113 F (30GX,HXA)
85 F (30HXC)
HD.P.B XXX.X °F HEAD PRESSURE SETPOINT B
Default: 113 F (30GX,HXA)
85 F (30HXC)