What to do if Carrier CRECOMZR067A01 Fan damper does not close completely?
- MMrs. Angela Camacho DDSAug 3, 2025
Ensure the damper linkage or hub allows the damper to close completely. Inspect these components to verify full closure is possible.
What to do if Carrier CRECOMZR067A01 Fan damper does not close completely?
Ensure the damper linkage or hub allows the damper to close completely. Inspect these components to verify full closure is possible.
Why Carrier CRECOMZR067A01 control asks for dry bulb temperature when using enthalpy sensors?
If the humidity sensor in the enthalpy sensors fails, the backup algorithm in the control will default to the temperature sensor in the enthalpy sensor. This is why the control asks for a dry bulb changeover temperature.
How to recalibrate Carrier CRECOMZR067A01 enthalpy sensor?
The sensor cannot be recalibrated in the field. However, the ADVANCED menu allows input of a limited offset in temperature and humidity for each sensor connected to the economizer.
Why is Carrier Fan outdoor temperature reading inaccurate?
Check the sensor wiring. Enthalpy sensors should be wired to the S-Bus terminals, and temperature sensors should be wired to the OAT and MAT terminals.
Model Number | CRECOMZR067A01 |
---|---|
Category | Fan |
Brand | Carrier |
Type | Ceiling Fan |
Reversible Motor | Yes |
Provides an overview of the EconoMi$er X system and its capabilities.
Details the field-installed accessories available for the EconoMi$er X system.
Outlines compliance with California Title 24 and ASHRAE 90.1 standards.
Provides specific installation instructions for 48/50LC 07-12 unit models.
Details the installation of the HH57AC081 Single Outside Air Enthalpy Sensor.
Instructions for installing the CRDIFRASN01A00 differential return air sensor kit.
Explains California Title 24 requirements for high temperature limit settings.
Details the setup and operation of Demand Controlled Ventilation using a CO2 sensor.
Describes how to set up remote monitoring for controller fault detection.
Describes the Honeywell W7220 controller used in the economizer system.
Explains the LCD interface and keypad functions of the W7220 controller.
Details how to use the navigation buttons for menus and settings.
Guides on using the keypad to navigate through the controller's menus.
Explains how to use the keypad to adjust settings and parameters.
Illustrates the hierarchy of menus and parameters available on the controller.
Details the adjustable setpoints for the economizer controller.
Covers system setup parameters like fan type, equipment, and occupancy.
Procedures for testing damper operation and controller outputs.
Details the wiring connections for the W7220 economizer module.
Describes the LCD timeout and screen saver function of the controller.
Explains how the economizer functions during cooling mode.
Explains how the economizer functions during heating mode.
Addresses how settings are restored after power interruptions.
Explains alarm messages displayed by the economizer module.
Guides on how to clear identified alarms from the system display.