F80CTL and G80CTL: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
25
 
Inspections before the sale and at the time of installation will determine
the acceptability of the chimney or the need for repair and/or (re)lining.
Refer to Fig. 33 to perform a chimney inspection. If the inspection of a
previously used tile-lined chimney:
a. Shows  signs  of  vent  gas  condensation,  the  chimney  should  be
relined in accordance with local codes and the authority having
jurisdiction. The chimney should  be relined with a  listed metal
liner, Type-B vent, or a listed chimney adapter kit shall be used to
reduce  condensation.  If a  condensate  drain is required by  local
code,  refer  to  the  NFPA  54/ANSI  Z223.1,  Section  12.10  for
additional information on condensate drains.
b. Indicates the chimney exceeds the maximum permissible size in
the tables, the chimney should be rebuilt or relined to conform to
the  requirements  of  the  equipment  being  installed  and  the
authority having jurisdiction. 
A  chimney  without  a  clay  tile  liner,  which  is  otherwise  in  good
condition,  shall  be  rebuilt  to  conform  to ANSI/NFPA  211  or  be  lined
with a UL listed metal liner or  UL listed Type-B vent. Relining with a
listed metal liner or Type-B vent is considered to be a vent-in-a-chase. 
If  a  metal  liner  or  Type-B  vent  is  used  to  line  a  chimney,  no  other
appliance shall  be  vented into  the  annular space  between  the chimney
and the metal liner. 
EXTERIOR MASONRY CHIMNEY FAN + NAT
INSTALLATIONS WITH TYPE-B DOUBLE-WALL
VENT CONNECTORS 
E
NFPA & AGA
 
Appliance Application Requirements 
Appliance operation has a significant impact on the performance of the
venting  system.  If  the  appliances  are  sized,  installed,  adjusted,  and
operated properly, the venting system and/or the appliances should not
suffer  from  condensation  and  corrosion.  The  venting  system  and  all
appliances  shall  be  installed  in  accordance  with  applicable  listings,
standards, and codes. 
The furnace should be sized to provide 100 percent of the design heating
load requirement plus any margin that occurs because of furnace model
size  capacity  increments.  Heating  load  estimates  can  be  made  using
approved  methods  available  from  Air  Conditioning  Contractors  of
America  (Manual  J); American  Society  of  Heating,  Refrigerating,  and
Air-Conditioning  Engineers;  or  other  approved  engineering  methods.
Excessive oversizing of the furnace could cause the furnace and/or vent
to fail prematurely. 
When  a  metal  vent  or  metal  liner  is  used,  the  vent  must  be  in  good
condition  and  be  installed  in  accordance  with  the  vent  manufacturer’s
instructions. 
To prevent condensation in the furnace and vent system, the following
precautions must be observed:
1. The return-air temperature must be at least 60°F db except for brief
periods of time during warm-up from setback at no lower than 55°F
(13°C) db or during initial start-up from a standby condition.
2. Adjust the gas input rate per the installation instructions. Low gas
input rate causes low vent gas temperatures, causing condensation
and  corrosion  in  the  furnace  and/or  venting  system.  Derating  is
permitted only for altitudes above 2000 Ft. (610 M).
3. Adjust the air temperature rise to the midpoint of the rise range or
slightly  above.  Low  air  temperature  rise  can  cause  low  vent  gas
temperature and potential for condensation problems.
4. Set  the  thermostat  heat  anticipator  or  cycle  rate  to  reduce  short
cycling.
Air  for  combustion  must  not  be  contaminated  by  halogen  compounds
which  include  chlorides,  fluorides,  bromides,  and  iodides.  These
compounds  are  found  in  many  common  home  products  such  as
detergent, paint,  glue, aerosol spray, bleach,  cleaning solvent, salt,  and
air freshener, and can cause corrosion of furnaces and vents. Avoid using
Table 7 – Minimum Allowable Input Rating of
Space-Heating Appliance in Thousands of Btuh per Hour
VENT HEIGHT
FT. (M)
INTERNAL AREA OF CHIMNEY
SQ. IN. (SQ. MM)
12
(7741)
19
(12258)
28
18064)
38
(24516)
Local 99% Winter Design Temperature: 17 to 26 degrees F
*
*. The 99.6% heating (db) temperatures found in the 1997 or 2001 ASHRAE 
Fundamentals Handbook, Climatic Design Information chapter, Table 1A 
(United States) and 2A (Canada) or the 2005 ASHRAE Fundamentals 
handbook, Climatic Design Information chapter, and the CD-ROM included 
with the 2005 ASHRAE Fundamentals Handbook.
6 0 55 99 141
8 52 74 111 154
10 NR 90 125 169
15 NR NR 167 212
20 NR NR 212 258
30 NR NR NR 362
Local 99% Winter Design Temperature: 5 to 16 degrees F
*
6 NR 78 121 166
8 NR 94 135 182
10 NR 111 149 198
15 NR NR 193 247
20 NR NR NR 293
30 NR NR NR 377
Local 99% Winter Design Temperature: -10 to 4 degrees F
*
6 NR NR 145 196
8 NR NR 159 213
10 NR NR 175 231
15 NR NR NR 283
20 NR NR NR 333
30 NR NR NR NR
Local 99% Winter Design Temperature: -11 degrees F or
 lower
Not recommended for any vent configuration.
Table 8 – Combined Appliance Maximum Input Rating 
in Thousands of Btuh per Hour
VENT HEIGHT
FT (M)
INTERNAL AREA OF CHIMNEY 
SQ. IN. (SQ. MM) 
12
(7741) 
19
(12258) 
28
(18064) 
38
(24516) 
6 (1.8) 74  119  178  257 
8 (2.4) 80  130  193  279 
10 (3.0) 84  138  207  299 
15 (4.5) NR  152  233  334 
20 (6.0) NR  NR  250  368 
30 (9.1) NR  NR  NR  404 
CAUTION
!
BURN HAZARD
Failure to follow this caution may result in personal injury. 
Hot  vent  pipe  is  within  reach  of  small  children  when  installed  in
downflow position. 
See the following instruction.