F80CTL and G80CTL: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
30
e. After  component  test  is  completed,  one  or  more  status  codes
(heartbeat, 2+5) will flash. See component test section of service
label (Fig. 49) in furnace for explanation of status codes. 
NOTE: To  repeat component test, turn setup switch SW1-6 OFF, then
back ON.
5. Turn setup  DIP switch  SW1-6 OFF.  Reconnect R  lead  to furnace
control  board,  release  blower  door  switch  and  reinstall  blower
access door.
6. Operate furnace per instruction on inner door.
7. Verify  furnace  shut  down  by  lowering  thermostat  setting  below
room temperature.
8. Verify  furnace  restarts  by  raising  thermostat  setting  above  room
temperature.
ADJUSTMENTS 
A93059
Fig. 47 – Orifice Hole
Furnace gas input rate on rating plate is for installations at altitudes up to
2000  Ft.  (610  M).  Furnace  input  rate  must  be  within  +/-2  percent  of
furnace  rating  plate  input.  For  altitudes  above  5500  Ft.  (1676  M),  a
field-supplied  high  altitude  pressure  switch  is  required.  Perform  the
following steps:
1. Determine the correct gas input rate. 
The  input  rating  for  altitudes  above  2,000  ft.  (610  M)  must  be
reduced by 4 percent for each 1,000 ft. (305 M) above sea level. 
For  installations below  2000  Ft.  (610  M),  refer  to  the  unit  rating
plate. For installations above 2000 Ft. (610 M), multiply the input
on  the  rating  plate  by  the  de-rate  multiplier  in  Table 10  for  the
correct input rate. 
2. Determine the correct orifice and manifold pressure adjustment. All
models in all positions except Low NOx models in downflow and
horizontal  positions  use  Table 15  (22,000  Btuh  per  burner.)  Low
NOx models in downflow or horizontal positions must use Table 16
(21,000 Btuh per burner.) See input listed on rating plate.
a. Obtain average yearly gas heat value (at installed altitude) from
local gas supplier.
b. Obtain  average  yearly  gas  specific  gravity  from  local  gas
supplier.
c. Find installation altitude in Tables 15 or 16.
d. Find closest natural gas heat value and specific gravity in Tables
15 or 16.
e. Follow  heat  value  and  specific  gravity  lines  to  point  of
intersection to find orifice size and low-and high-heat manifold
pressure settings for proper operation.
f. Check  and  verify  burner  orifice  size  in  furnace.  NEVER
ASSUME ORIFICE SIZE. ALWAYS CHECK AND VERIFY.
NOTE: If orifice hole appears damaged or it is suspected to have been
redrilled,  check  orifice  hole  with  a  numbered  drill  bit  of  correct  size.
Never redrill an orifice. A burr-free and squarely aligned orifice hole is
essential for proper flame characteristics.
g. Replace  orifice  with  correct  size,  if  required  by  Table 15  or
Table 16.  Use  only  factory-supplied  orifices.  See  Example
below. 
 
 
3. Adjust manifold pressure to obtain low fire input rate, see Fig. 21.
a. Turn gas valve ON/OFF switch to OFF.
b. Remove manifold pressure tap plug from gas valve.
c. Connect  a  water  column  manometer  or  similar  device  to
manifold pressure tap.
d. Turn gas valve ON/OFF switch to ON.
e. Move  setup  SW1-2  on  furnace  control  to  ON  position  to  lock
furnace in low-heat operation, see Table 14 and Fig. 32.
f. Manually close blower door switch.
g. Jumper R and W/W1 thermostat connections on control to start
furnace, see Fig. 32.
WARNING
!
FIRE HAZARD
Failure  to  follow  this  warning  could  result  in  personal  injury,  death
and/or property damage. 
DO  NOT  bottom  out  gas  valve  regulator  adjusting  screw.  This  can
result in unregulated manifold pressure and result in excess overfire and
heat exchanger failures.
CAUTION
!
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in reduced furnace life. 
DO NOT redrill orifices. Improper drilling (burrs, out-of-round holes,
etc.)  can  cause  excessive  burner  noise  and  misdirection  of  burner
flames.  This  can  result  in  flame  impingement  of  heat  exchangers,
causing failures, see Fig. 47. 
EXAMPLE: 0–2000 ft. (0-610 M) altitude
For 22,000 Btuh per burner application use Table 15. 
Heating value = 1000 Btuh/cu ft. 
Specific gravity = 0.62 
Therefore: Orifice No. 43* 
Manifold pressure: 3.7-In. W.C. for high-heat 
1.6-In. W.C. for low-heat 
* Furnace is shipped with No. 43 orifices. In this example all main burner orifices are the 
correct size and do not need to be changed to obtain proper input rate.
Table 10 – Altitude Derate Multiplier for U.S.A. 
ALTITUDE 
FT. (M)
PERCENT 
OF DERATE 
DERATE MULTIPLIER 
FACTOR* 
0–2000
(0-610) 
0  1.00 
2001–3000
(610-914) 
8–12  0.90 
3001–4000
(914-1219) 
12–16  0.86 
4001–5000
(1219-1524)
16–20  0.82 
5001–6000
1524-1829)
20–24  0.78 
6001–7000
(1829-2134)
24–28  0.74 
7001–8000
(2134-2438) 
28–32  0.70 
8001–9000
(2438-2743)
32–36  0.66 
9001–10,000
(2743-3048)
36–40  0.62